Technical data

What this chapter contains

This chapter contains the technical specifications of the drive, e.g. the ratings, sizes
and technical requirements, provisions for fulfilling the requirements for CE and
other markings and warranty policy.
Reference:

Environmental Conditions

System connection
Voltage, 3-phase:
Voltage deviation:
Rated frequency:
Static frequency deviation:
Dynamic: frequency range:
df/dt:
* = 0.5 to 30 cycles.
Please note: Special consideration must be taken for voltage devi-
ation in regenerative mode.
Degree of protection
Converter Module and
options (line chokes, fuse
holder,
field supply unit, etc.):
Enclosed converters:
Paint finish
Converter module:
Enclosed converter:
Size
Sound pressure level L
tance)
as module
D1
55 dBA
D2
55 dBA
D3
60 dBA
D4
66...70 dBA,
depending on fan
D5
73 dBA
D6
75 dBA
D7
82 dBA
Effect of the site elevation above sea level on the converter's load capacity
100
90
80
70
60
50
1000
2000
Current reduction to (%)
Hardware extension
Hardware extension
DCS800 1131 Programming target
Branching units NDBU-95
230 to ≤ 1000 V acc. to IEC 60038
±10% continuous; ±15% short-time *
50 Hz or 60 Hz
50 Hz ±2 %; 60 Hz ±2 %
50 Hz: ±5 Hz; 60 Hz: ± 5 Hz
17 % / s
IP 00 / NEMA TYPE OPEN
IP 20/21/31/41
light grey RAL 9002
light grey RAL 7035
(1 m dis-
Vibration
P
enclosed conv.
54 dBA
55 dBA
1.5 mm, 2...9 Hz
73 dBA
0.5 g, 9...200 Hz
77 dBA
78 dBA
0.3 mm, 2...9 Hz
73 dBA
0.1 g, 9...200 Hz
80 dBA
3000
4000
5000 m
3ADW000194R0611 DCS800 Hardware Manual f us
RAIO Analog I/O Extension
RDIO Digital I/O Extension
Environmental limit values
Permissible cooling air temp.
- at converter module air inlet:
with rated DC current:
w. different DC curr. acc. Fig.
below:
- Options:
Relative humidity (at 5...+40°C): 5 to 95%, no condensation
Relative humidity (at 0...+5°C):
Change of the ambient temp.:
Storage temperature:
Transport temperature:
Pollution degree (IEC 60664-1,
IEC 60439-1):
Vibration class
(IEC-60721-3-3)
Site elevation
<1000 m above M.S.L.:
>1000 m above M.S.L.:
Shock
Transport in
original Package
as module
1.2 m
7 g / 22 ms
1.0 m
0.25 m
4 g / 22 ms
Shock monitor
Effect of the ambient temperature on the converter module load capacity
110
100
90
80
70
30
35
Current reduction to (%) for converter modules
publ.no.:3AFE64484567
publ.no.:3AFE64485733
publ.no.:3ADW000199
publ.no.:3ADW000100
0 to +55°C
0 to +40°C
+30 to +55°C
0 to +40°C
5 to 50%, no condensation
< 0.5°C / minute
-40 to +55°C
-40 to +70°C
2
3M3 - D1...D4
3M1 - D5...D7
100%, without current reduction
with curr. reduct., see Fig. below
Short circuit withstand rating
The DCS800 is suitable for use in a circuit capa-
ble of delivering not more than:
65 kA rms symmetrical amps at maximum
600 VAC
100 kA rms symmetrical amps at maxi-
mum 600 VAC
40
45
50
55°C
Technical data
69