ABB DCS800 Hardware Manual page 39

Hide thumbs Also See for DCS800:
Table of Contents

Advertisement

For compliance with the protection objectives of the
German EMC Act (EMVG) in systems and
machines, the following EMC standards must be sat-
isfied:
Product Standard EN 61800-3
EMC standard for drive systems (PowerDriveSys-
tem), interference immunity and emissions in resi-
dential areas, enterprise zones with light industry
and in industrial facilities.
This standard must be complied with in the EU for
satisfying the EMC requirements for systems and
machines!
Second environment (industry) with PDS categories C3, C4
satisfied
PDS category C3
Medium-voltage network
Supply transformer for a
Industrial zone
residential area (rating
normally ≤ 1.2 MVA)
Earthed
neutral
Earthed 400-V network
with neutral conductor;
3~ ≤ 400 A
Mains filter
Line reactor +
Line reactor
Y-capacitor
Converter
Converter
M
M
M
M
Operation at low-voltage network together with
other loads of all kinds, apart from some kinds
of sensitive communication equipment.
For emitted interference, the following apply:
EN 61000-6-3
EN 61000-6-4
For interference immunity, the following apply:
EN 61000-6-1
EN 61000-6-2
* The old generic standards are given in brackets
Not applicable
on customer's request
satisfied
Industrial
zone
Converter
transformer
Line reactor
Converter
M
M
Operation with separate power converter transformer. If there
are other loads at the same secondary winding, these must be
able to cope with the commutation gaps caused by the power
converter. In some cases, commutating reactors will be
required.
3ADW000194R0611 DCS800 Hardware Manual f us
Specialised basic standard for emissions in light industry can
be satisfied with special features (mains filters, screened power
cables) in the lower rating range *(EN 50081-1).
Specialised basic standard for emissions in industry *(EN
50081-2)
Specialised basic standard for interference immunity in residen-
tial areas *(EN 50082-1)
Specialised basic standard for interference immunity in industry.
If this standard is satisfied, then the EN 61000-6-1 standard is
automatically satisfied as well *(EN 50082-2).
satisfied
PDS category C4
Medium-voltage network
Converter
transformer
with earthed
iron core
(and earthed
I > 400 A
screen where
and/or
appropriate)
U > 500 V
Line reactor
Converter
Converter
M
M
M
M
Planning the electrical installation
39
Standards
EN 61800-3
EN 61000-6-3
EN 61000-6-4
EN 61000-6-2
EN 61000-6-1
Classification
The following overview uti-
lises the terminology and
indicates the action
required in accordance with
Product Standard
EN 61800-3
For the DCS800 series, the
limit values for emitted inter-
ference are complied with,
provided the measure indi-
cated is carried out. PDS of
category C2 (formerly
restricted distribution in first
environment) is intended to
be installed and commis-
sioned only by a profes-
sional (person or
organization with necessary
skills in installing and/or
commissioning PDS includ-
ing their EMC aspects).
For power converters with-
out additional components,
the following warning
applies:
This is a product of cate-
gory C2 under IEC 61800-
3:2004. In a domestic/res-
idential environment this
product may cause radio
interference in which
case supplementary miti-
gation measures my be
required.
The field supply is not
depicted in this overview
diagram. For the field cur-
rent cables, the same rules
apply as for the armature-
circuit cables.
Legend
Screened cable
Unscreened cable with restriction

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents