ABB DCS800 Hardware Manual page 38

Hide thumbs Also See for DCS800:
Table of Contents

Advertisement

38
EMC filters
You will find further infor-
mation in publication:
Technical Guide chapter:
EMC Compliant Installa-
tion and Configuration for a
Power Drive System
Not applicable
Medium-voltage network
Residential area
Earthed
neutral
Earthed public 400-V
network with neutral
conductor
Mains filter
Line reactor
Converter
Converter
M
M
Operation at public
An isolating transformer
low-voltage network
with an earthed screen
together with other
and earthed iron core
loads of all kinds.
renders mains filter and
line reactor superfluous.
Planning the electrical installation
The paragraphs below describe selection of the electri-
cal components in conformity with the EMC Guideline.
The aim of the EMC Guideline is, as the name implies,
to achieve electromagnetic compatibility with other
products and systems. The guideline ensures that the
emissions from the product concerned are so low that
they do not impair another product's interference immu-
nity.
In the context of the EMC Guideline, two aspects must
be borne in mind:
•the product's interference immunity
First environment (residential area with light industry) with PDS category C2
Not applied, since category C1 (general distribution sales channel) excluded
Supply transformer for a residential
area (rating normally ≤ 1,2 MVA)
3ADW000194R0611 DCS800 Hardware Manual f us
•the product's actual emissions
The EMC Guideline expects EMC to be taken into
account when a product is being developed; however,
EMC cannot be designed in, it can only be quantita-
tively measured.
Note on EMC conformity
The conformity procedure is the responsibility of both
the power converter's supplier and the manufacturer of
the machine or system concerned, in proportion to their
share in expanding the electrical equipment involved.
satisfied
Medium-voltage network
Light industry
Earthed public 400-V
network with neutral
conductor
Mains filter
Line reactor +
Line reactor
Y-capacitor
Converter
Converter
M
M
M
M
Operation at public
low-voltage network
together with other
loads of all kinds.
satisfied
Supply transformer for a residential
area (rating normally ≤ 1.2 MVA)
Earthed
neutral
Earthed public 400-V
network with neutral
conductor
Mains filter
Line reactor
Converter
Converter
M
M
Operation at public
An isolating transformer
low-voltage network
with an earthed screen
together with other
and earthed iron core
loads of all kinds.
renders mains filter and
line reactor superfluous.
Residential area