Station status 2
Table 4-8
Bit
0
1: The DP slave must be reconfigured.
1
1: A diagnostic message is queued. The DP slave will not operate unless
the error is eliminated (static diagnostic message).
2
1: The bit is always "1" on the DP slave.
3
1: The watchdog is activated for this DP slave.
4
1: The DP slave has received a "FREEZE" control command.*
5
1: The DP slave has received a "SYNC" control command.
6
0: The bit is always "0".
7
1: When the station status is being read from the DP master, the bit is "1" if
the DP slave has been disabled in the DP master.
The DP slave is disabled; in other words, it is isolated from the current
process.
*
When the control command "FREEZE" is set, the diagnostic messages are also frozen.
Station Status 3
Table 4-9
Bit
0 to 7
0: The bits are always "0".
ET 200eco Distributed I/O Station
A5E00158716-02

Structure of station status 2 (byte 1) ET 200eco

Structure of station status 3 (byte 2) ET 200eco

Commissioning and diagnostics
Meaning
Meaning
4-13