Installation
Installation of the terminal block
1. Insert the terminal block into the I/O module.
2. Bolt the terminal block to the I/O module (with a torque of 1 to 1.3 nm). Tighten
the screws evenly in diagonally opposite sequence.
The terminal block is equipped with four captive screws (see Figure 2-2).
Figure 2-2
Note
The protection type IP 65, IP 66 or IP 67 is only ensured after the terminal block is
screwed tight onto the I/O module!
2.4

Label replacement

Properties
You can use these labels to identify each of the I/O module's channels and the
terminal block. The system is supplied with snap–on labels:
• 8 labels on the I/O module
• 1 label on the terminal block
Requirements
Replacement labels are available on order. For order numbers please refer to
Appendix A.
2-4
2
Inserting and screw–tightening the terminal block at the I/O module
2
2
2
1
ET 200eco Distributed I/O Station
A5E00158716-02