11.12 Checking Standing Wave Ratio of Feeder Cables

1.
2.
3.

11.13 Checking Indoor and Outdoor Environment

Check if:
1.
2.
3.
4.
After the antennae are installed and all feeder cables are connected, measure the
standing wave ratio of them.
Measure one end of the indoor 1/2" jumper cable, which is connected with the
cabinet, with the tester. The standing wave ratio should be lower than 1.5. It is
best to be lower than 1.3.
Record the VSWR value and provide the VSWR test diagram.
All waste materials are cleared, and the outdoor environment is clean.
The equipment room is clean and neat, and all things needed are arranged in
order.
No waste materials such as cable ties, cables and desiccant bags are left
around/under the shelf and under the raised floor.
The front door, rear door and side panels are cleaned so that no touch prints can
be seen. There is no dust or scrap in the cabinet.
Chapter 11 Hardware Installation Check
11-9