3.8
3.9
3.10
RAYCHEM-AR-H60624-40X0iOpsManual-EN-1905
The controller will notify the user if any part (user, maintenance, profile 1, profile 2, factory) of the settings
are lost. If factory settings are lost, the unit must be replaced. As a precautionary measure, the loss of
either the factory or user data will prevent the device from turning on the heat trace.
The Low Storage Capacity alarm indicates that this memory is nearing its end of life, so plans should be
made to replace the controller.

Graphical User Interface (GUI)

The Elexant 4010i/4020i has an integrated resistive touch screen to provide
accessible and intuitive interaction with the controller. The GUI can be set to display its text in five
languages (English, French, German, Spanish, and Russian). The controller can be configured and
monitored using the GUI. See Section 5.1 for more details.

LED Status Indicators

The front panel of the Elexant 4010i/4020i Heat Trace Controller has 4 LED indicators to indicate conditions.
LED
STATUS
STATUS
OFF
Flashing Red/Green
Flashing Yellow/Green
Flashing Yellow/Red
Solid Red
Solid Green
OUTPUT
OFF
Solid Orange
Flashing Orange
COMM
OFF
Flashing Green
Flashing Red
ALARM
OFF
Solid Red

Table 10 - LED Status Indicators

GUI Screen Saver Mode

The Elexant 4010i/4020i controller has a built-in screen saver feature that automatically turns on every
hour after the device is powered up. When the screen saver is activated, the idle screen shows an alter-
nate version of the display for 1 minute in which it flips the state of every pixel on the screen.
nVent RAYCHEM Elexant 4010i/4020i User Manual
DESCRIPTION
No power/Faulty LED
Calibrated / Unlocked
Uncalibrated / Locked
Uncalibrated / Unlocked
Device Reset Alarm Active
Normal Operation/No Internal Fault
Control Output OFF
Control Output ON 100%
Output Duty Cycle Mode
No Communication
Receive Active
Transmit Active
No Alarm
Alarm Condition
|