2.6.14
Alarm Relay
The alarm relay (terminals 7,8,9 of TB3) is energized in the normal state (when there are no alarms),
and configured as Fail Safe. The alarm relay connections provide a Form C dry contact, rated at 277 V
maximum (3 A).
Figure 21 - Alarm Relay
2.6.15
Digital Inputs
The Elexant 4010i/4020i provides multi-purpose inputs (terminals 10,11,12 of TB2) for connection to
external dry (voltage-free) contacts or DC voltages for extending the functionality of the controller. Digital
Inputs support a maximum of 100 Ohm loop resistance or may be used with 5 to 24 VDC @ 1 mA maxi-
mum voltages.
Figure 22 - Digital Inputs
nVent RAYCHEM Elexant 4010i/4020i User Manual
|