Alarm Relay; Digital Inputs - nvent RAYCHEM Elexant 4010i User Manual

Heat trace controller
Table of Contents

Advertisement

RAYCHEM-AR-H60624-40X0iOpsManual-EN-1905
2.6.14

Alarm Relay

The alarm relay (terminals 7,8,9 of TB3) is energized in the normal state (when there are no alarms),
and configured as Fail Safe. The alarm relay connections provide a Form C dry contact, rated at 277 V
maximum (3 A).
Figure 21 - Alarm Relay
2.6.15

Digital Inputs

The Elexant 4010i/4020i provides multi-purpose inputs (terminals 10,11,12 of TB2) for connection to
external dry (voltage-free) contacts or DC voltages for extending the functionality of the controller. Digital
Inputs support a maximum of 100 Ohm loop resistance or may be used with 5 to 24 VDC @ 1 mA maxi-
mum voltages.
Figure 22 - Digital Inputs
nVent RAYCHEM Elexant 4010i/4020i User Manual
|
nVent.com
20

Advertisement

Table of Contents
loading

This manual is also suitable for:

Raychem elexant 4020i

Table of Contents