Profibus (Optional); Table 7- Rs485 Settings; Table 8 - Ethernet Settings - nvent RAYCHEM Elexant 4010i User Manual

Heat trace controller
Table of Contents

Advertisement

RAYCHEM-AR-H60624-40X0iOpsManual-EN-1905
Variable
Description
Address
Modbus Station Address used to identify the unit.
Baud Rate - the rate at which communications occur on
Baud
the network.
Defines the type of parity bit to be used with any of the
Parity
three serial communications ports.
Defines the number of stop bits used with any of the three
Stop Bits
serial communications ports.
Transmit
Sets the time the unit will wait after it receives a message
Delay
before it replies.

Table 7- RS485 Settings

3.3.1.2 Ethernet
A 10/100Mbps Ethernet LAN connection may be used by the Elexant 4010i/4020i for communicating
with remote devices using the Modbus/TCP protocol. An Ethernet connection can be made via the RJ45
connector at the top of the unit. Configuration parameters and defaults are shown below.
Variable
Description
Allows the unit to use Dynamic Host
Enable DHCP
Configuration Protocol
Defines the Ethernet Port IP Ad-
Network Address
dress.
A 32-bit number that masks the
Network Mask
network address and divides it into
network address and host address.
Serves as the forwarding host to
other networks when no other route
Default Gateway
specification matches the destina-
tion IP address.

Table 8 - Ethernet Settings

3.3.2

Profibus (Optional)

The Elexant 4020i is available with an optional Profibus communications port. It is also a master-slave
protocol similar to Modbus but has the ability to support multiple masters. Like Modbus, Profibus also
runs on an RS-485 link. Profibus connectivity is made via a specific DB9 connector and Profibus cable.
Variable
Description
Address
Profibus Station Address used to identify the unit.
nVent RAYCHEM Elexant 4010i/4020i User Manual
Default
Range/Options
1
1 to 247
9600
9600, 19200, 38400, 57600
None
None, Odd, Even
1
1, 2
20
0 to 5000 ms
Default
Range/Options
Enabled
Enabled, Disabled
192.168.1.100
0 to 255 for each address field.
255.255.255.0
0 to 255 for each mask field.
192.168.1.1
0 to 255 for each mask field.
Default
Range/Options
5
1 to 125
|
nVent.com
33