1734-IE4S Safety Analog Input Module Features

• Connection of up to four voltage or current sensors.
• Sensor power outputs are individually current-limited and monitored.
• Measurement of process variables, such as temperature, pressure, or flow
rate.
• Seven configurable input ranges
(±10V, ±5V, 0...5V, 0...10V, 4...20 mA, 0...20 mA, Tachometer).
• Tachometer mode converts 24V DC switching signals into pulses per
second.
• Single-channel or dual-channel for SIL 3-rated safety devices and
applications.
• Dual-channel mode evaluates the consistency between two input signals
(channels), which allows use of the module in applications rated up to and
including SIL CL3/PLe/Cat. 4.
• You can configure a discrepancy time to control how long two channels are
allowed to be discrepant before a fault is declared.

Programming Requirements

Use the minimum software versions listed here.
Cat. No.
Studio 5000 Environment
(1)
Version
1734-IB8S,
21
1734-OB8S
1734-IE4S
21
(1) This version or later.
(2) If you are using digital POINT Guard I/O modules with the analog POINT Guard I/O module, you need to update the add-on
profiles to version 2.02.004 or later for the modules to be compatible with version 18 or later of RSLogix 5000 software and the
Studio 5000 environment. To find add-on profiles, go to http://www.rockwellautomation.com/support.
(3) Dual-channel Analog (DCA) safety application instruction is available in RSLogix 5000 software, version 20 or later and Studio
5000 environment, version 21 and later.
Rockwell Automation Publication 1734-UM013J-EN-P - July 2014
POINT Guard I/O Overview
RSLogix 5000 Software
RSNetWorx for DeviceNet
(1)
Version
Software Version
(EtherNet/IP Network)
(DeviceNet Network)
(2)
17
9
(3)
18
10
Chapter 1
(1)
19