Chapter 9 Using Sto Function - Mitsubishi Electric Melservo-J4 MR-J4-DU*B4-RJ100 Series Instruction Manual

General purpose ac servo sscnet iii/h interface drive unit
Table of Contents

Advertisement

9
USING STO FUNCTION
For items other than the ones described in this chapter, refer to chapter 13 in "MR-J4-_B_(-RJ) Servo
Amplifier Instruction Manual".
Wiring example
In the parallel drive system, multiple drive units drive one servo motor. Wire the STO signal to all the drive units.
The following shows a system that drives a servo motor with four MR-J4-DU_B4-RJ100 drive units and four MR-CV_ power
regeneration converter units connected. For the number of drive units required to be connected to one servo motor, refer to
the following.
Page 13 Combinations of power regeneration converter units, drive units, and servo motors
Servo system controller
SSCNET III/H
MC
*1
Power supply
*1 For parallel drive systems, the magnetic contactor turns off when STO is inputted (when [AL. 95] has occurred). The setting of [Pr. PF07
Magnetic contactor shut-off selection at STO input (_ x _ _)] is invalid.
9 USING STO FUNCTION
72
Safety controller
STO1
STO2
Encoder master
servo amplifier
MC
*1
Power supply
Emergency stop
switch or others
TOFB (from the encoder master servo amplifier and the respective encoder slave servo amplifiers)
Encoder slave
servo amplifier 1
MC
*1
Power supply
Encoder slave
servo amplifier 2
MC
*1
Power supply
Encoder slave
servo amplifier 3