Zone 1, 21 - Type Of Protection "Flameproof; (Enclosure); Ex-Marking; Electrical And Temperature Data - ABB SwirlMaster FSS430 Commissioning Instructions

Vortex & swirl flowmeter
Hide thumbs Also See for SwirlMaster FSS430:
Table of Contents

Advertisement

2.4

Zone 1, 21 - type of protection "flameproof

(enclosure)"

2.4.1

Ex-marking

ATEX
Order code
Type examination certificate
II 2 G Ex d ia IIC T6 Gb/Ga – II 2 D Ex tb IIIC T85 °C Db
(-40 °C < Ta < +75 °C) supply voltage 42 V DC,
Um: 45 V
IECEx
Order code
Certificate of conformity
Ex d ia IIC T6 Gb/Ga-Ex tb IIIC T85 °C Db
(-40 °C < Ta < +75 °C) supply voltage 42 V DC,
Um = 45 V
FM approval for USA and Canada
Order code
XP-IS (US) CL I/DIV I/GP BCD, DIP CL II, III/DIV I/GP EFG
XP-IS (Canada) CL I/DIV I/GP BCD, DIP CL II, III/DIV I/GP EFG
CL I, ZONE 1, AEx/Ex d ia IIC T6 -40 °C < Ta < +75 °C
TYPE 4X Tamb = 85 °C "Dual seal device"
NEPSI
Order code
Ex d ia IIC T6 Gb / Ga
DIP A21 Ta 85 °C
For electrical parameters, see certificate GYJ14.1088X
Power supply
Ex d ia Gb/Ga: U
= 12 ... 42 V DC
B
Switch output
The switch output is designed as an optoelectronic coupler or
a NAMUR contact (in accordance with DIN 19234).
— When the NAMUR contact is closed, the internal
resistance is approx. 1000 Ω.
— When the contact is open, the internal resistance is
> 10 kΩ.
The switch output can be changed over to "optoelectronic
coupler" if required.
— NAMUR with switching amplifier
— Switch output:
Ex d ia: Ui = 45 V
IMPORTANT
The power supply and the digital output must be either only
intrinsically safe or only non-intrinsically safe. A combination of
the two is not permitted.
Intrinsically safe circuits must have potential equalization in
place along the entire length of the cable of the circuit.
12 CI/FSS/FSV430/450-EN Rev. D | SwirlMaster FSS430, FSS450 VortexMaster FSV430, FSV450
A9
FM13ATEX0057X
N3
IECEx FME 13.0004X
F1
S1
2.4.2

Electrical and temperature data

R [k ]
Ω
B
1,8
1,6
1,4
1,2
1,0
0,9
0,8
0,6
0,4
0,2
0
10
12
20
Ex A /
i
IS
Ex
d XP
Fig. 3:
Power supply in Zone 1, explosion protection
The minimum voltage U
of 12 V is based on a load of 0 Ω.
S
U
Supply voltage
S
R
Maximum permissible load in the power supply circuit,
B
e.g. indicator, recorder or power resistor.
Power supply / current output / HART output
Terminals
PWR/COMM + / PWR/COMM -
U
45 V
M
Zone 1: Ex d ia IIC T6 Gb/Ga
T
= -40 ... 75 °C
amb
Zone 21 Ex tb IIIC T85 °C Db
T
= -40 ... 75 °C
amb
XP-IS (US) CL I/DIV I/GP BCD, DIP CL II, III/DIV I/ GP EFG
XP-IS (Kanada) CL I/DIV I/GP BCD, DIP CL II, III/ DIV I/GP EFG
CL I, ZONE 1, AEx/Ex d ia IIC T6 -40 °C < Ta < +75 °C
TYPE 4X Tamb = 75 °C „Dual seal device"
30
40 42
/
U [V]
50
S
G11792