ABB SwirlMaster FSS430 Commissioning Instructions page 35

Vortex & swirl flowmeter
Hide thumbs Also See for SwirlMaster FSS430:
Table of Contents

Advertisement

Operating mode /
Description
order code
Gas Power / NG4
Energy flow of the gaseous
medium
Bio Act. Volume / NG5
Partial actual volume flow of
biogas
Bio Std/Norm Vol. 9) /
Partial standard volume flow of
NG6
biogas
Steam Act. Volume /
Actual volume flow of the
NS1
vaporous medium
Steam Mass (internal
Mass flow of the vaporous
density determination)
medium
10)
/ NS2
Steam Mass (external
Mass flow of the vaporous
density determination)
medium
11)
/ NS2
2) The highest priority of the device is to record the density via the analog input, as long as the analog input is activated as a density input. If the analog input is not
available as a density input, the system attempts to record the density via the HART input. If both the analog input and the HART input are deactivated as a density
input, the system uses the default density value.
3) The connection via the analog input or HART input is described in the chapter titled „Electrical connections" on page 21.
5) The highest priority of the device is to record the temperature via the analog input, as long as the analog input is activated as a temperature input. If the analog input is
not available as a temperature input, the system attempts to record the temperature via the HART input. If both the analog input and the HART input are deactivated
as a temperature input, the system uses the default density value.
6) The highest priority of the device is to record the pressure via the analog input, as long as the analog input is activated as a pressure input. If the analog input is not
available as a pressure input, the system attempts to record the pressure via the HART input. If both the analog input and the HART input are deactivated as a
pressure input, the system uses the default pressure value.
8) The biogas proportion can be determined via the analog input, HART input or default setting. The highest priority of the device is to record the biogas proportion via
the analog input, as long as the analog input is activated as a biogas proportion input. If the analog input is not available as a biogas proportion input, the system
attempts to record the biogas proportion via the HART input. If both the analog input and the HART input are deactivated as a biogas proportion input, the system
uses the default biogas proportion value.
9) In order to implement the "Bio Std/Norm Vol." mode, as a precondition the required parameters from one of the NG2 modes must be available.
10) In order to implement the "Steam Mass" mode with internal density determination, the selection "Calculated from..." must be set in the menu Device Setup /
Plant/Customized / Compensation Setting -> Steam Density Selec..
11) In order to implement the "Steam Mass" mode with external density determination, the selection "Ext.-Density" must be set in the menu Device Setup /
Plant/Customized / Compensation Setting -> Steam Density Selec..
Additional parameters required
Energy density
Biogas proportion
8)
n/a
Operating pressure
3) 6)
Operating temperature
3) 5)
Operating density
2) 3)
SwirlMaster FSS430, FSS450 VortexMaster FSV430, FSV450 | CI/FSS/FSV430/450-EN Rev. D 35
Parameter setting
Device Setup / Plant/Customized /
Compensation Setting -> Gas Energy Density
Via analog input:
Input/Output / Field Input / Analog In Value ->
Gas Content
Via HART input:
Input/Output / Field Input / Hart In Value ->
Gas Content
Default setting for the density:
Device Setup / Plant/Customized /
Compensation Setting -> Preset Density
Via analog input:
Input/Output / Field Input / Analog In Value ->
Pressure
Via HART input:
Input/Output / Field Input / Hart In Value ->
Pressure
Default setting for the pressure value:
Device Setup / Plant/Customized /
Compensation Setting -> Preset Pressure
With internal temperature sensor.
No information required, the measured value
from the temperature sensor is used.
Default setting for the temperature value:
Device Setup / Plant/Customized /
Compensation Setting -> Preset Int.Temp
Via analog input:
Input/Output / Field Input / Analog In Value ->
Density
Via HART input:
Input/Output / Field Input / Hart In Value ->
Density
Default setting for the density:
Device Setup / Plant/Customized /
Compensation Setting -> Preset Density