Technical Data; Units Data - REMKO EMT 100 Assembly And Operating Instructions Manual

Inverter heat pump
Table of Contents

Advertisement

REMKO EMF / EMT
2

Technical data

2.1

Units data

Series
Function
System
Heat pump manager
Storage tank for hydraulic decoupling of volumetric flows
Electric booster heating / rated output
Water heating
Heating output min / max
Heating output / compressor frequency / COP
W35
Heating output / compressor frequency / COP
W35
Heating output / compressor frequency / COP
W35
Heating output / compressor frequency / COP
W35
Heating output / compressor frequency / COP
W35
Cooling output min. / max.
Cooling output / compressor frequency / EER
W7
Cooling output / compressor frequency / EER
W7
Service limits, heating
Service limits, cooling
Supply-temperature, heating water
Min. Supply-temperature, cooling
Refrigerant / pre-charge quantity outdoor unit
Refrigerant / pre-charge quantity for up to 10 m length of
ordinary pipe
Refrigerant connection
Max. permissible single refrigerant pipe length.
Max. permissible single refrigerant pipe height.
Power supply
Starting current
Rated current consumption for A7/W35
Rated power consumption for A7/W35
8
kW
kW
kW/Hz/COP
1)
for A10/
kW/Hz/COP
1)
for A7/
kW/Hz/COP
1)
for A2/
4)
kW/Hz/COP
for A2/
kW/ Hz/COP
1)
for A-7/
kW
2)
kW/Hz/COP
for A35/
kW/Hz/COP
2)
for A27/
°C
°C
°C
°C
-- / kg
g / m
Inches
m
m
V / Hz
A
A
kW
EMF 100
EMT 100
Heating or Cooling
Split-Air/Water
Multitalent or Multitalent Plus
optional
Series 160 l
optional
Series / 9,0
optional
Series
1,1 - 10,2
8,7 / 58 / 4,9
8,1 / 58 / 4,4
4,7 / 58 / 3,0
6,3 / 73 / 2,5
4,5 / 58 / 2,7
1,6 - 9,1
6,2 / 3,5 / 74
6,4 / 3,9 / 74
-18 bis +45
+15 bis +45
up to +50
up to +7
2)
R 410A
/ 1,9
30
¼ / ⅝
50
30
230/1~ / 50
12,5
13
1,84