Installation, Mounting Outdoor Module - REMKO EMT 100 Assembly And Operating Instructions Manual

Inverter heat pump
Table of Contents

Advertisement

REMKO EMF / EMT
4.3
Installation, mounting out-
door module
Outdoor module installation location
n
The device may be attached only to a load-
bearing structure or wall. Ensure that the out-
door module is installed only vertically. The
installation site should be well ventilated.
n
To minimise noise, install floor consoles with
vibration dampers and a considerable distance
from acoustically-reflective walls to minimise
noise.
The minimum clearances specified on the next
n
page should be maintained when carrying out
the installation. These minimum distances
serve to ensure unrestricted air intake and
exhaust. Additionally, there must be adequate
space available for installation, maintenance
and repair.
n
If the outdoor module is erected in an area of
strong winds, then the device must be pro-
tected against them (Fig. 27). The snow line is
to be observed during installation (Fig. 28).
n
The outdoor module must always be installed
on vibration dampers. Vibration dampers pre-
vent the transmission of vibrations through the
floor or walls.
n
A heated, condensate catch-pan ensures that
condensation from the pan can drain off.
Ensure that the condensate is prevented from
freezing so that it can drain off (gravel,
drainage). The Water Ecology Act is to be
observed.
n
If there is insufficient space under the device
for the refrigerant lines, then the pre-cut
recesses can be removed from the lower
enclosure-panel and the pipes guided through
these openings.
n
During installation, add about 20 cm to the
expected snow depth to guarantee unimpeded
intake and exhaust of outdoor air year round.
(Fig. 28).
n
The installation site of the outdoor module
should be agreed together with the operator
primarily so that operating noise is minimised
and not in terms of "short routes". Thanks to
the split-design technology there are a great
deal of different installation options with almost
identical efficiency available.
28
Wind
Fig. 27: Protection from wind
Snow + 20 cm
Fig. 28: Protection from snow
NOTICE!
The site for the outdoor module must be
selected so that machinery noise that occurs
disturbs neither the residents nor the facility
operator. Observe the TA-noise specifications
as well as the table containing the drawings
relating to sound pressure levels.