The outdoor- and the indoor modules are con-
nected with two copper pipes of refrigerator
quality having the dimensions ¼" and ⅝"
(REMKO special accessory).
n
Observe the permitted bending radius for the
refrigerant pipes during installation in order to
prevent kinks. Never bend a pipe twice in the
same place in order to prevent embrittlement
or crack formation.
n
Assure suitable fastening and insulation when
laying the refrigerant pipes.
n
The copper pipes are to be flared to make the
connections to the modules. In doing so, check
that the flare has the correct shape and suit-
able union nuts. (Fig. 34 to Fig. 36).
Fig. 34: Deburring the refrigerant line
1. Refrigerant line
2. Deburrer
34
1
2
Fig. 35: Flanging the refrigerant line
1. Flanging tool
Fig. 36: Correct flange shape
Copper piping Out-
side diameterer
¼" or 6,35 mm
⅝" or 15,88 mm
1
Flare dimensions ø A
10,15 - 10,65 mm
19,3 - 19,7 mm