Parameter settings
Parameter
T-Flow Day
Only if parameter [HC Function] = 1:
Setting the inflow target temperature for the heating circuit during the heating time when
in operating mode: "Automatic 1", "Automatic 2", "Heating".
T-Flow Night
Only if parameter [HC Function] = 1:
Setting the inflow target temperature for the heating circuit during the setback time when
in operating mode: "Automatic 1", "Automatic 2", "Reducing".
Max T-Flow
The inflow temperature determined for the heating circuit is limited to the maximum val-
ue set here.
If an additionally connected mixed heating circuit demands a higher temperature for the
Daikin Altherma EHS(X/H), this is taken into account. This means that the heat internal
circulation pump for the Daikin Altherma EHS(X/H) runs all the time when this is
switched on. If the connected heating circuit supplies underfloor heating, a mechanical
temperature limiter must be fitted to prevent overheating the screed.
Min T-Flow
The inflow temperature determined for the heating circuit is limited to the minimum value
set here.
HC Adaption
Only if the room station
Off: Deactivated
On: Activated = Start a one-off automatic adaptation of the heating curve.
Requirements:
- Outside temperature < 8 °C
- Setting the operating mode: "Automatic 1" or "Automatic 2"
- Duration of the setback phase must be at least 6 hours
Function: At the start of the setback time the current room temperature is set as the tar-
get value for the following 4 hours. The heating curve is determined by the Control from
the inflow target temperatures that are necessary to maintain this room temperature.
If the automatic adjustment of the heating curve is interrupted, the function pauses until
it is performed successfully on the next day or until it is ended by setting the parameter
to "Off" or by changing the current operating mode.
The hot water generation and the heating-up optimisation are blocked during the auto-
matic heating curve adapting.
Cooling (Can be used only if the assigned heat generator has a cooling function.)
Start T-Out Cooling
Only if parameter [HC Function] = 0:
Setting from which outside temperature the cooling operation with the highest cooling
infeed target temperature [T-Flow Cooling start] starts (setting condition: operating
mode "Cooling").
Max T-Out Cooling
Only if parameter [HC Function] = 0:
Setting to determine from which outdoor temperature the lowest cooling flow tempera-
ture [T-Flow Cooling max] is stipulated (setting condition: operating mode "Cooling").
T-Flow Cooling start Only if parameter [HC Function] = 0:
Setting the cooling inflow target temperature at the start of cooling mode (outside tem-
perature = parameter [Start T-Out Cooling]).
T-Flow Cooling max Only if parameter [HC Function] = 0:
Setting the minimum cooling inflow target temperature. This is kept constant relative to
the outside temperature (parameter [Max T-Out Cooling]).
Min T-Flow Cooling
Only if parameter [HC Function] = 0:
Setting the absolute lower limit of the cooling inflow target temperature. The limitation is
effective if a lower cooling inflow target temperature is determined based on other pa-
rameter settings.
T-Flow Cooling
Only if parameter [HC Function] = 1:
Setting the cooling inflow target temperature (fixed value) when cooling mode is active.
Cooling Setpoint adj Parallel displacement of the cooling characteristic curve to match the set value.
Tab. 5-3 Parameter in rotary switch setting "Configuration" level "HC Configuration"
Operating instructions
36
Description
is connected and assigned to the heating circuit.
Access
Setting range
Factory
Min / Max
setting
BE
HF
E
E
20 - 90 °C
40 °C
E
E
10 - 90 °C
10 °C
N
E
20 - 90 °C
55 °C
N
E
10 - 90 °C
10 °C
N
E
Off
Off
On
E
E
15 - 45 °C
24 °C
E
E
20 - 45 °C
35 °C
E
E
5 - 25 °C
18 °C
E
E
5 - 25 °C
8 °C
N
E
5 - 25 °C
18 °C
E
E
8 - 30 °C
18 °C
E
E
-5.0 to +5.0 kW
0.0 K
008.1420844 – 05/2014
Increment
1 °C
1 °C
1 °C
1 °C
-
1 °C
1 °C
1 °C
1 °C
1 °C
1 °C
1 K
Daikin RoCon HP