Parameter
Air Purge
Activation of automatic bleeding of the Daikin Altherma EHS(X/H) and the connected
heating circuit (see chapter 3.6.10).
Off: Deactivated
On: Start of Air Purge
PWM Config
Max Perform Pump
Upper limit for modulation of the pump output
Min Perform Pump
Lower limit for modulation of the pump output
Sensor Config
Outside Config
Configuration of the optional external temperature sensor RoCon OT1:
Off: No sensor evaluation
On: Sensor evaluation activates (if an outdoor temperature sensor is not connected, a
fault message is generated.)
Storage Config
Configuration of water heating:
inactive; no function for hot water generation.
Sensor: Function for hot water generation is activated. A circulating tank temperature
sensor is evaluated for hot water generation (if no circulating tank temperature sensor is
connected, a fault message is generated).
Thermostat: Function for hot water generation is activated. A thermostatic switch (On /
Off) is evaluated for hot water generation, and where "Open brackets" are evaluated as
"No demand".
Pressure Config
Configuring the sensor for assessment of the system water pressure:
Off: No sensor evaluation
On: Sensor evaluation activated (if no pressure sensor is connected, a fault message is
generated.)
Outside Temp Adap
Individual adapting for the measured value of the outdoor temperature relevant for the
Control.
Terminaladress
Setting the data bus address for system access. The set value must be applicable for the
entire system. Confirmation of this parameter using the rotary switch reinitialises the con-
troller.
System Config
System configuration of the unit, consisting of the sensor configuration and bus configu-
ration. If you answer "Yes" to the enquiry about using the standard configuration when
starting the unit for the first time, the basic configuration for the installed heat generator
will be activated automatically.
Confirmation of this parameter setting as "Inactive" or "Delete" using the rotary switch
reinitialises the controller. A fault message follows. After this the rotary switch must be
set to the position "Info". Use the rotary switch to select the required menu item.
HC Assignment
Display only on connected
Allocation of the room station to the heating circuit to be operated.
The direct heating circuit of the Daikin Altherma EHS(X/H) is set as standard to "0"
(see section 5.12, parameter [Unmixed Circ Config])
Tab. 5-1 Parameter in rotary switch setting "Configuration" level "Setup"
Daikin RoCon HP
Daikin Control
008.1420844 – 05/2014
Description
room station:
5
x
Parameter settings
Access
Setting range
Factory
Min / Max
setting
BE
HF
N
E
Off
Off
On
N
E
20 - 100 %
100 %
N
E
10 - 100 %
50 %
N
E
Off
Off
On
N
E
Inactive
Sensor
Sensor
Thermostat
N
E
Off
On
On
N
E
-5.0 to +5.0 K
0.0 K
N
E
Off, 0 - 9
Off
N
E
Inactive
Active
Active
Delete
N
E
Off, 0 - 15
Off
Operating instructions
Increment
-
1 %
1 %
-
-
-
0.1 K
1
-
1