130 Maintenance
Capacitor failure is usually followed by damage to the unit and an input cable fuse failure,
or a fault trip. Contact ABB if capacitor failure is suspected. Replacements are available
from ABB. Do not use other than ABB specified spare parts. Contact an ABB service
representative for spare parts and repair services.

Reforming the capacitors

The capacitors must be reformed if the drive has not been powered (either in storage or
unused) for a year or more. The manufacturing date is on the type designation label. For
information on reforming the capacitors, see Converter module capacitor reforming
instructions (3BFE64059629 [English]) in the ABB Library (https://library.abb.com/en).
If the drive module has been stored for one to three years, turn on the mains power for 30
minutes without load, then continue as usual.
If the drive module has been stored for less than a year, continue as usual.