Neighboring network
Point of measurement
Low voltage
Equipment
2. An EMC plan for preventing disturbances is drawn up for the installation. A template is
available from the local ABB representative.
3. The motor and control cables are selected as specified in the hardware manual.
4. The drive is installed according to the instructions given in the hardware manual.
WARNING!
A drive of category C4 is not intended to be used on a low-voltage public network
which supplies domestic premises. Radio frequency interference is expected if
the drive is used on such a network.

Compliance with EN 61800-3:2004

Definitions

EMC stands for Electromagnetic Compatibility. It is the ability of electrical/electronic
equipment to operate without problems within an electromagnetic environment. Likewise,
the equipment must not disturb or interfere with any other product or system within its locality.
First environment includes establishments connected to a low-voltage network which supplies
buildings used for domestic purposes.
Second environment includes establishments connected to a network not supplying domestic
premises.
Drive of category C2: drive of rated voltage less than 1000 V and intended to be installed
and started up only by a professional when used in the first environment. Note: A professional
is a person or organization having necessary skills in installing and/or starting up power
drive systems, including their EMC aspects.
Drive of category C3: drive of rated voltage less than 1000 V and intended for use in the
second environment and not intended for use in the first environment.
Drive of category C4: drive of rated voltage equal to or above 1000 V, or rated current equal
to or above 400 A, or intended for use in complex systems in the second environment.

Category C3

The drive complies with the standard with the following provisions:
1. The drive is installed according to the instructions given in the appropriate drive hardware
manual.
2. Maximum motor cable length is 100 meters (328 ft).
Medium voltage network
Low voltage
Equipment
(victim)
Equipment
Supply transformer
Static screen
Drive
Technical data 161