ABB ACS880-37LC Hardware Manual page 54

Industrial drives
Hide thumbs Also See for ACS880-37LC:
Table of Contents

Advertisement

54 Mechanical installation
5. Center the Axilock connectors onto the gaps between coolant pipe ends. Tighten the
connector screws to the torque indicated on the connector label.
6. Fasten the front and rear posts of the joining cubicle to the posts of the other section
with 14 screws (7 per post). Tighten the screws to 5 N·m (3.7 lbf·ft).
7. Fasten the second section to the floor.
1
4
4
8. Connect the PE busbars using the M10 bolts and nuts included. Tighten to 35...40 N·m
(25...30 lbf·ft).
a Plain washer
b Spring washer
c Bolt and nut
3
5
35...40 N·m
(25...30 lbf·ft)
a
a
4
c
b

Advertisement

Table of Contents
loading

Table of Contents