Ac Power; Fluid Outlet Line - Graco SaniForce Operation

Drum unloader sdu system
Hide thumbs Also See for SaniForce:
Table of Contents

Advertisement

Installation

AC Power

NOTICE
Branch circuit protection and power disconnect to
be provided by the installer per local code.
AC power is required for an unloader with an
electro-pneumatic control panel.
1. Route wires to control panel through electrical
conduit. Attach conduit using hole on bottom
right hand side of enclosure with a type 4X rated
conduit hub.
2. Attach the power system ground wire to the
chassis ground lug (as shown) with 14 AWG
stranded copper wire. Torque to 35 in-lbs (3.95
N•m).
14
3. Connect equipment to 100 – 240 VAC, single
phase, 50/60 Hz, 15 A service with 14 AWG
stranded copper wire. Attach to L1 and L2 on
power switch as shown. Torque to 8 in-lbs (0.9
N•m).

Fluid Outlet Line

Connect a grounded, flexible fluid hose (S) to the fluid
outlet port. The port is 2.0 in (50.8 mm) tri-clamp.
3A5402B