Installer Setup (Isu) Table - Honeywell TH8321 Product Data

Smart thermostat
Hide thumbs Also See for TH8321:
Table of Contents

Advertisement

ISU
Installer Setup
Number
Name
Residential
101
Application
Commercial
[Select Thermostat Name]
103
Thermostat Name
Non-Programmable
104
Thermostat Type
Programmable
Fahrenheit
105
Temperature Scale
Celsius
Wired/Internet
106
Outdoor Temp
No
Conv. Forced Air
200
Heating System
Heat Pump
Radiant Heat
Other
None (Cool Only)
Heat Pump:
201
Heating Equipment
Air to Air Heat Pump
Geothermal
Geothermal Radiant
0
202
Radiant Heat
1
Stages
2
None
203
Radiant Stage 1
U1
None
205
Geo Forced Air
Cooling Only
Heating and Cooling
O (O/B on Cool)
206
Reversing Valve
B (O/B on Heat)
Table 2. Installer Setup (ISU) Table.
Settings
Default
Residential
Thermostat
Programmable
Fahrenheit
No
Conv. Forced Air
Air to Air Heat Pump
Default varies based
on previous selections
Heating and Cooling
O/B on Cool
VISIONPRO® 8000 SMART THERMOSTAT
Residential,
Commercial
or Both
Both
Both
The Web Interface displays the name of the
thermostat that you enter on this screen.
Both
Both
Both
Select Wired/Internet to indicate that you are going
to connect a wired outdoor sensor or connect to the
internet. This will allow you to configure settings
prior to the Internet being connected.
Select No if you are not going to connect to an
outdoor sensor or the Internet.
Both
For Dual Fuel, choose Heat Pump.
Both
This ISU is not displayed when ISU 200 Heating
System is set to Conv. Forced Air, Radiant Heat,
Other or None (Cool Only).
See "Geothermal Radiant Heat" beginning on
page 55.
Both
Select the number of radiant heat stages.
Both
This ISU is only displayed when ISU 200 is Heat
Pump and 201 Heating Equipment is Geothermal
Radiant.
Geothermal Radiant Heat must be wired to U1
terminals.
U1 is a normally open set of dry contacts. U1
requires power from the system transformer or a
separate transformer.
Both
This thermostat has the capability of controlling
Geothermal Radiant Heat, Geothermal Forced Air
and Backup Heat.
If this thermostat is not controlling the Geothermal
Forced Air System, select None. This setting is
typically used if the thermostat is only controlling
Geothermal Radiant Heat.
If this thermostat is using the Geothermal Forced Air
System for cooling and not for heating, select
Cooling Only.
If this thermostat is using the Geothermal Forced Air
System for both heating and cooling, select Heating
and Cooling.
Both
Only displayed if the equipment type is Air to Air
Heat Pump, Geothermal or Geothermal Radiant.
11
Notes
33-00096—04