Honeywell TH8321 Product Data page 27

Smart thermostat
Hide thumbs Also See for TH8321:
Table of Contents

Advertisement

ISU
Installer Setup
Number
Name
Unlocked
411
Keypad Lockout
Partially Locked
Fully Locked
No
500
Wired Sensor on S
Terminals
Yes
No
500
Wired Remote
Indoor Sensor
Yes
No
500
Wired Outdoor
Sensor
Yes
No
500
Wired Discharge
Yes
Sensor
[Select Indoor Sensor Name]
501
Indoor Sensor
Name
S1
502
Indoor Sensor
10K
503
Indoor Sensor Type
20K
Use [T-Stat Sensor]
Use T-Stat Sensor for Temp Ctrl -
504
for Temp Ctrl
Yes or No
S1
505
Outdoor Sensor
S1
509
Discharge Sensor
10K
510
Discharge Sensor
20K
Type
Off
511
A-Coil Low Temp.
Cutoff
35° F to 65° F (in 5° F
increments)
Table 2. Installer Setup (ISU) Table. (Continued)
Settings
Default
Unlocked
No
No
No
No
Indoor Sensor
10K:
if ISU 101 Application
is Residential
20K:
if ISU 101: Application
is Commercial
Sensors are Averaged
(T-Stat Sensor and
Remote)
10K
Off
VISIONPRO® 8000 SMART THERMOSTAT
Residential,
Commercial
or Both
Both
Unlocked: User has access to all thermostat settings.
Partially Locked: User can modify only temperature
settings.
Fully Locked: User cannot modify any settings.
Both
This ISU is only displayed if ISU 106 was configured
to Wired/Internet.
Select Yes if a wired indoor, outdoor, or discharge
sensor is wired to S1.
Both
Select Yes if a wired indoor sensor is wired to S1.
Both
Select Yes if a wired outdoor sensor is wired to S1.
Both
Select Yes if a wired discharge sensor is wired to S1
Both
Select a name (location) of the Wired Remote Indoor
Sensor.
Both
Confirms type of sensor wired to S1.
Both
Select 10K or 20K based on the sensor installed.
Refer to resistance values below:
C7189U1005 = 10K ohm
C7772 = 20K ohm
TR21 = 20K ohm
TR21-A = 10K ohm (IMPORTANT - the TR21-A must
be used in combination with a TR21 sensor or
another TR21-A sensor for the thermostat to
calculate the correct indoor temperature reading).
See "Wiring guide — Wired Indoor Sensors"
beginning on page 89 for information on the sensor
type you should select based on how the sensors are
wired. For example, you would select 20K when you
have two TR21-A (10K) sensors wired in series.
Both
Only displayed when a wired indoor sensor is
configured. Select Yes if you want the thermostat to
average with wired indoor sensor. Select No if you
want to sense temperature only at the wired sensor.
Both
Confirms type of sensor wired to S1.
Both
Confirms type of sensor wired to S1.
Both
Select 10K or 20K based on the sensor installed.
Refer to resistance values below:
50062329-001 = 10K ohm
32005180-002 = 10K ohm
C7735A1000 = 10K ohm
C7770A = 20K ohm
C7041 = 20K ohm
Both
If an optional Discharge Sensor is used, this feature
can help prevent icing on the air conditioning A-Coil.
When temperature reaches the limit you set,
compressor(s) will shutoff while the system fan
continues to run, until the temperature rises to a safe
level.
27