VISIONPRO® 8000 SMART THERMOSTAT
ISU
Installer Setup
Number
Name
Off
408
Max. Cool Recovery
Ramp Rate
1° F/hr to 20° F/hr
Off
408
Max. Cool Recovery
-20° F to 100°F
Outdoor Temp
No
409
Adaptive Recovery
Yes
50° F to 99° F
410
Minimum Cool
Setpoint
40° F to 90° F
410
Maximum Heat
Setpoint
33-00096—04
Table 2. Installer Setup (ISU) Table. (Continued)
Settings
Default
6° F/hr
70° F
Yes
50° F
90° F
Residential,
Commercial
or Both
Commercial
Off: The cooling system will begin recovery at the
time that is scheduled.
When a Maximum Recovery Ramp Rate is set, the
thermostat will begin recovery early to ensure the
temperature is reached at the scheduled time.
Set a Maximum Recovery Ramp Rate based on the
rate that the cooling system can recover at for a mild
day in your region. Default setting is 6° F / hour.
Set an Outdoor Temperature that is representative of
a mild day in your region to be associated with the
Maximum Recovery Ramp Rate.
The thermostat will begin recovery at the optimal
time based on a calculated ramp rate, allowing the
system to recover on time and save energy during
changing outdoor conditions.
During recovery, the setpoint changes at a rate in
degrees per hour depending on the outdoor
temperature.
Commercial
Off: The cooling system will begin recovery at the
time that is scheduled.
When a Maximum Recovery Ramp Rate is set, the
thermostat will begin recovery early to ensure the
temperature is reached at the scheduled time.
Set a Maximum Recovery Ramp Rate based on the
rate that the cooling system can recover at for a mild
day in your region. Default setting is 6° F / hour.
Set an Outdoor Temperature that is representative of
a mild day in your region to be associated with the
Maximum Recovery Ramp Rate.
The thermostat will begin recovery at the optimal
time based on a calculated ramp rate, allowing the
system to recover on time and save energy during
changing outdoor conditions.
During recovery, the setpoint changes at a rate in
degrees per hour depending on the outdoor
temperature.
Residential
No: The system will begin heating or cooling
recovery at the scheduled time.
Yes: The thermostat will begin heating or cooling
recovery early to ensure that the temperature is
reached at the scheduled time. The thermostat will
adjust the start time of the equipment based on how
quickly the scheduled temperature was reached on
previous days. See page 51 for more information on
Adaptive Intelligent Recovery.
Both
The user cannot set the temperature below this level.
Both
The user cannot set the temperature above this level.
26