Honeywell TH8321 Product Data page 16

Smart thermostat
Hide thumbs Also See for TH8321:
Table of Contents

Advertisement

VISIONPRO® 8000 SMART THERMOSTAT
ISU
Installer Setup
Number
Name
Comfort
303
Cool Differential
Stage 2
1.0° F to 3.5° F from setpoint (in
0.5° F increments)
Comfort
303
Cool Differential
1.0°F - 4.0°F from setpoint (in
Stage 3
0.5° F increments)
Comfort
305
Heat Differential
Stage 2
1.0° F to 3.5° F from setpoint (in
0.5° F increments)
Note: Depending on
the application, the
text displayed on
the screen may
show the specific
heating equipment
type
Comfort
305
Heat Differential
Stage 3
1.0° F to 4.0° F from setpoint (in
0.5° F increments)
Note: Depending on
the application, the
text displayed on
the screen may
show the specific
heating equipment
type
33-00096—04
Table 2. Installer Setup (ISU) Table. (Continued)
Settings
Default
Comfort
Comfort
Comfort
Comfort
Residential,
Commercial
or Both
Both
ISU 301 Control Options must be set to Advanced to
view or adjust this ISU.
This ISU is only displayed when the thermostat is set
to 2 cool stages.
The indoor temperature must rise to the selected
differential setting before the thermostat turns on
the stage of cooling. For example, if stage 2 is set to
2° F (1.0° C), the indoor temperature must be 2° F
(1.0° C) away from the setpoint before stage 2 turns
on. When set to Comfort, the thermostat uses the
stage of cooling as needed to keep the indoor
temperature within 1° F (0.5° C) degree of the
setpoint.
Commercial
ISU 301 Control Options must be set to Advanced to
view or adjust this ISU.
This ISU is only displayed when the thermostat is set
to 3 cool stages.
The indoor temperature must rise to the selected
differential setting before the thermostat turns on
the stage of cooling. For example, if stage 3 is set to
2° F (1.0° C), the indoor temperature must be 2° F
(1.0° C) away from the setpoint before stage 3 turns
on. When set to Comfort, the thermostat uses the
stage of cooling as needed to keep the indoor
temperature within 1° F (0.5° C) degree of the
setpoint.
Both
ISU 301 Control Options must be set to Advanced to
view or adjust this ISU.
This ISU is only displayed for conventional systems
that have 2 heat stages.
The indoor temperature must drop to the selected
differential setting before the thermostat will turn on
the stage of heating. For example, if stage 2 is set to
2° F (1.0° C), the indoor temperature must be 2° F
(1.0° C) away from the setpoint before stage 2 turns
on. When set to Comfort, the thermostat will use the
stage of heating as needed to keep the indoor
temperature within 1° F (0.5° C) degree of the
setpoint.
Both
ISU 301Temperature Control Options must be set to
Advanced to view or adjust this ISU.
This ISU is only displayed for conventional systems
that have 3 heat stages.
The indoor temperature must drop to the selected
differential setting before the thermostat will turn on
the stage of heating. For example, if stage 3 is set to
2° F (1.0° C), the indoor temperature must be 2° F
(1.0° C) away from the setpoint before stage 3 turns
on. When set to Comfort, the thermostat will use the
stage of heating as needed to keep the indoor
temperature within 1° F (0.5° C) degree of the
setpoint.