VISIONPRO® 8000 SMART THERMOSTAT
ISU
Installer Setup
Number
Name
Off
921
Dehumidifier Filter
Reminder
30, 60, Calendar Days
3 to 12 Calendar Months (in 1
month increments)
None
1000
Ventilation Type
ERV / HRV
Passive (Fan Only)
Fresh Air Damper
None
1002
Ventilation Wiring
U1
ASHRAE
1005
Ventilation Method
Percent On Time
Tstat Controls Fan
1006
Vent Fan Control
Equip Controls Fan
1 to 6
1009
Number of
Bedrooms
1000 to 5000 sq. ft. (in 100 sq.
1009
Size of House
ft. increments)
(90 to 460 sq. m.)
30 to 350 CFM (in 5 CFM
1010
Ventilation Rate
increments)
(850 - 9900 LPM)
10% to 100% (in 10%
1012
Vent Percent On
increments)
Time
33-00096—04
Table 2. Installer Setup (ISU) Table. (Continued)
Settings
Default
Off
None
Thermostat defaults to
the unused U1
terminal.
Defaults to
ASHRAE
when ISU 101
Application is set to
Residential.
Percent on Time is the
only choice when ISU
101 Application is set
to Commercial.
Tstat Controls Fan
2 bedrooms
1000 sq. feet
150
30%
Residential,
Commercial
or Both
Both
Both
None: The thermostat does not control ventilation.
ERV/HRV: The thermostat controls an Energy
Recovery Ventilator or Heat Recovery Ventilator for
ventilation.
Passive (Fan Only): The thermostat turns on the fan
for ventilation.
Fresh Air Damper: The thermostat turns on the fan
and opens a fresh air damper for ventilation.
Both
Number of Outputs:
TH8321 Thermostat: U1 terminals
U1 are dry contacts that require power. See "Wiring
IAQ Equipment or a Heat/Cool Stage to the U1
Terminals" beginning on page 86.
Both
See "Ventilation Control Methods (ISU 1005)"
beginning on page 67.
Both
Tstat Controls Fan: The thermostat turns on the
ventilation equipment and the fan when ventilation
is needed.
Equip Controls Fan: The thermostat turns on the
ventilation equipment when ventilation is needed.
The fan is controlled by the equipment.
Residential
This ISU is only displayed when ISU 1005
Ventilation Method is set to ASHRAE (Residential
only).
Residential
This ISU is only displayed when ISU 1005
Ventilation Method is set to ASHRAE (Residential
only).
Residential
This ISU is only displayed when ISU 1005
Ventilation Method is set to ASHRAE (Residential
only).
Both
The thermostat operates ventilation equipment
based on a percentage entered in the installer setup
(ISU 1012). For example, if Percent on Time is set to
50%, the ventilation equipment will run at random
times during a 1 hour period until it reaches a 50%
run time (approximately 30 minutes).