Perform High Level Supervision Test - Emerson Rosemount 5300 Manual Supplement

Level transmitter, high level supervision
Hide thumbs Also See for Rosemount 5300:
Table of Contents

Advertisement

Manual Supplement
5

Perform High Level Supervision test

5.1
Perform High Level Supervision test using Rosemount
Radar Master
Prerequisites
The product surface level should be at least 20 in. (500 mm) below the
reference reflector during the test.
The product surface level cannot be within 6 in. (150 mm) of the reference
reflector. The device will exit the test mode if the level rises within this area
during test, and instead output the current level measurement reading. It
will not enter the test mode if the surface already is within this distance.
WARNING
During the test the device will not output measurement values
corresponding to the product surface level. Make sure systems and people
relying on measurement values from the device are made aware of the
changed conditions.
Procedure
1. Start Test Mode.
Device will now output the level corresponding to the position of the
reference reflector echo. The text
device display if test is successful.
2. Verify that the output from the device corresponds to the alarm limit
in the host system.
3. End test mode by clicking Start/Stop Test Mode again.
(The device will automatically exit the test mode after 30 minutes
[default]).
5.2
Perform High Level Supervision test using AMS Device
Manager and handheld communicator
Prerequisites
The product surface level should be at least 20 in. (500 mm) below the
reference reflector during the test.
22
a) Select Setup → Advanced.
b) Click the Level Supervision tab.
c) Click Start/Stop Test Mode.
will appear on the
HLS Test OK
Rosemount 5300 Level Transmitter
April 2019