Omron RX2 Series User Manual page 169

Driveprogramming, cx-drive
Hide thumbs Also See for RX2 Series:
Table of Contents

Advertisement

The set values are scaled by the settings for AJ-24/AJ-25.
Parameter
No.
db-38
PID3 feedback data monitor
FA-38
PID3 Set Value
AJ-30
Set-point setting for PID3
db-57
PID3 output monitor
db-58
PID3 deviation monitor
The set values are scaled by the settings for AJ-44/AJ-45.
Parameter
No.
db-40
PID4 feedback data monitor
FA-40
PID4 Set Value
AJ-50
Set-point setting for PID4
db-59
PID4 output monitor
db-60
PID4 deviation monitor
DriveProgramming User's Manual (I622-E1)
7 Precautions for Use of Parameters for DriveProgramming
Description
a) Conversion (Scale adjustment)
b) Internal conversion (%)
*1. Equivalent to mon param read value (Same scale as
Description
a) Conversion (Scale adjustment)
b) Internal conversion (%)
*1. Equivalent to mon param read value (Same scale as
Data
= (PID1 scale adjustment (at 100%) [AJ-25] - PID1
scale adjustment (at 0%) [AJ-24])
/ 100.00 * [Input (%)] + PID1 scale adjustment (at 0%)
[AJ-24]
= ([Input (*1)] - PID1 scale adjustment (at 0%) [AJ-24])
/ (PID1 scale adjustment (at 100%) [AJ-25] - PID1
scale adjustment (at 0%) [AJ-24]) * 100.00
ones of AJ-24, 25)
Data
= (PID1 scale adjustment (at 100%) [AJ-45] - PID1
scale adjustment (at 0%) [AJ-44])
/ 100.00 * [Input (%)] + PID1 scale adjustment (at 0%)
[AJ-44]
= ([Input (*1)] - PID1 scale adjustment (at 0%) [AJ-44])
/ (PID1 scale adjustment (at 100%) [AJ-45] - PID1
scale adjustment (at 0%) [AJ-44]) * 100.00
ones of AJ-44, 45)
7
7 - 9