6 DriveProgramming Commands
 Example
In the above example, when X(00) is not 0, a forward operation is started with the "delay on" command
and the operation is stopped with the "delay off" command.
Block number
1
Assigns 200 to U(00).
2
Assigns 300 to U(01).
3
Jumps to the block 8: GT001 if X(00) is 0. Goes to the next step if X(00) is not 0.
4
Starts the timer (0) for the set value U(00) with the "delay on" command.
5 to 7
Assigns the status of FW to U(02) until FW changes to 1. Goes to the next step when FW changes
to 1.
8
Starts the timer (0) for the set value U(01) with the "delay off" command.
9 to 11
Assigns the status of FW to U(02) until FW changes to 0. Goes to the next step when FW changes
to 0.
12
Jumps to the block 3: loop_ unconditionally.