9.7 Detector Maintenance
The Searchzone Sonik App features a range of tools to aid the correct maintenance of the
Searchzone Sonik detector. After connecting to the detector via Bluetooth, you can perform
maintenance tasks, e.g., setting the maintenance flag, testing the output current loop, setting
relays, checking the function of the visual status indicator settings and running other diagnostic
tests.
Note
In order to adjust any of the detector settings the detector
must be placed into inhibit mode. The fault relay will change
state and the mA current loop will drop to the inhibit level.
Make sure that any effect on connected equipment is full
understood.
Connect to the detector and navigate to the main menu.
Select 'Maintenance'.
You can access the following:

• Event log

• Set maintenance flag
• Output test
• Diagnostics
Note
Unlike many ultrasonic gas leak detectors, Searchzone Sonik
does not require field calibration. Bump testing is achieved
using a cannister of compressed air.
9.7.1 Event Log
In the 'Maintenance' menu, tap on 'Event log'.
The log will open.
PN 2331M1220 Issue 1
Searchzone Sonik − Technical Manual
9 Mobile App
53
11/2018