Relays; Connections / Wiring Diagram - Honeywell SEARCHZONE SONIK SZSK-SMG Series Technical Manual

Table of Contents

Advertisement

The Searchzone Sonik features HART communications to provide access to the detector from a control system or hand-held device for
the purpose of configuration and to provide status and diagnostic information.
The total load resistance for the 4-20 mA current loop shall be less than 600 Ω, including the resistance of the 4-20 mA cable and
input impedance of the equipment to be connected. To ensure reliable HART communications, the minimum loop resistance is 250 Ω.
If HART communications is not required, the minimum loop resistance is 100 Ω.
If the 4-20 mA current loop is not used, a jumper must be connected between 4-20 mA+ (terminal 5) and 24V DC+ (terminal 8) and a
load resistor must be connected between 4-20 mA- (terminal 6) and 0V DC (terminal 9). It is recommended to use a 470 Ohm, 1/4 W
resistor (250 to 400 Ω if HART is required). With the 4-20mA current loop configured this way the HART facility can still be used with a
HART hand held unit using terminals 20 and 21 inside the wiring compartment.
2331D0194
CAUTION
The maximum permissible mA loop voltage is 32 VDC and the maximum current is 22 mA.
NOTES:
6.3 Relays
1. MATERIAL:
The Searchzone Sonik detector features 3 SPDT relay outputs for alarm and fault indication. Relay 1 is for alarm level 1, relay 2 is for
LABEL: 2331D0238
alarm level 2, and relay 3 indicates faults. The fault relay is normally energized and when energized indicates proper operation (no faults
INK RIBBON: BRADY R6000 THERMAL TRANSFER PRINTED - BLACK.
present).
In the event of power failure or fault, the COM-NO connection will open (the fault relay may be user configured as normally de-
2. THIS PRODUCT MUST BE RoHS COMPLIANT
energized.)
3. VALUES SHOWN ON ARE TYPICAL AND ARE FOR INFORMATION PURPOSES ONLY. PR
6.4 Connections / Wiring Diagram
DATA IS ENTERED BY THE PRODUCTION CONFIGURATION SYSTEM
Note
24 V pins number 7 & 8 and 0 V pins number 9 & 10 are internally linked.
PN 2331M1220 Issue 1
10 0V DC
9 0V DC
8 24V DC
7 24V DC
6 4-20mA -
5 4-20mA +
4 RS485 D
3 RS485 D
2 RS485 B
1 RS485 A
Registration
Serial Number:
1234567890
Activation Key:
ABCDEFGHIJKLM
Figure 21. Terminal Connector Label
Searchzone Sonik − Technical Manual
THIS DOCUMENT HAS BEEN GENERATED USING
INDESIGN AND MUST ONLY BE UPDATED BY IN
11 A2 COM
12 A2 NC
13 A2 NO
14 A1 COM
15 A1 NC
16 A1 NO
17 FLT COM
18 FLT NC
19 FLT NO
20 HART +
21 HART -
QR Code
QR Code
6 Electrical Installation
11/2018
32