Connect Wires To Pcb Terminals - Honeywell SEARCHZONE SONIK SZSK-SMG Series Technical Manual

Table of Contents

Advertisement

5.10 Connect Wires to PCB Terminals
CAUTION
Remove power from Searchzone Sonik before performing any electrical installation or maintenance.
CAUTION
The equipment features pluggable connectors that are mechanically locked into position. These are
not accessible by the user during normal operation.
1. Loosen the grub screw.
2. Unscrew the Searchzone Sonik wiring compartment cover.
3. Unscrew and remove the pluggable connectors.
4. Connect wires as per local procedures. The connectors are clearly identified. Refer to the diagrams and tables in the
Electrical Installation section of this manual for information on wiring.
5. Ensure that the O-rings on the detector body and in the end cap are properly fitted and not damaged.
6. Ensure that the threads of the wiring compartment cover are clean of dust and lubricated with a suitable anti-seize compound.
7. Screw on the wiring compartment cover.
8. Tighten the grub screw to a final torque of 1.1 Nm (0.81 lb-ft)
9. Ensure the horizontal M10 bolts are loosened by 2-3 turns.
10. Use the graduated adjustment and angle scale to aim the Detector to the required position.
11. IMPORTANT: First, tighten the left-facing horizontal M10 bolt to a final torque of 30 Nm (22 lb-ft).
12. IMPORTANT: Second, tighten the right-facing horizontal M10 bolt to a final torque of 30 Nm (22 lb-ft).
13. Fit the sunshade in place. Refer to section 5.11 Sunshade Installation for instructions.
PN 2331M1220 Issue 1
Figure 18. PCB Terminals
Left-facing horizontal M10 bolt
Searchzone Sonik − Technical Manual
5 Mechanical Installation
Wiring Compartment
Cover
Grub screw
11/2018
28