9.8 Detector Settings
You can view all of the detector settings, including firmware details and background levels, with an option to
export this data to a CSV file. (The CSV file is saved in the mobile device in location defined in the Application
Settings.)
To access the detector settings, tap on the 'SETTINGS' button from the Overview screen. You can also edit
some of the detector settings by tapping on the 'Edit' button.
The following values can be adjusted:
Detector ID
Operation mode
Algorithm mode
Inhibit level
Alarm set point
Warning level
Alarm 1 level
Fault level
Alarm 2 level
Over-range level
Alarm delay
Normal level
LED mode
LED intensity
Proof test interval
Alarm Latch
Loop current mode
Hart poll address
Fault Relay
Alarm 1 Relay
Alarm 2 Relay
Inhibit timeout period
Set Access Code
CAUTION
1. The default inhibit timeout is set 0 and the detector will remain in inhibit unless end user manually clears
the inhibit condition.
2. Changing the inhibit timeout settings (to, for example, 10 minutes) and saving the changes will NOT affect
the current session. The change in inhibit timeout will be made in the next session when end user puts the
detector into inhibit.
3. Loop current mode: Multidrop or Point-to-point
4. HART poll address: 0 to 63
PN 2331M1220 Issue 1
(minimum characters are 4; maximum characters are 26. Supports special
characters like !@#$%^&*()_ +{}|:"<>?[]\;',./-)
(Discrete or Proportional)
(Standard or Focused)
(Default value = 2 mA; Minimum value = 1 mA; Maximum value = 3.6 mA;
Step increments of 0.1 mA)
(40 dB to 120 dB)
(Default value = 3 mA; Minimum value = 0 mA; Maximum value = 4.0 mA;
Step increments of 0.1 mA)
(4.0 mA to 20.0 mA; step 0.1 mA; default 16.0 mA)
(Default value = 1 mA; Minimum value = 0 mA; Maximum value = 3.6 mA;
Step increments of 0.1 mA)
(4.0 mA to 20.0 mA; step 0.1 mA; default 20.0 mA)
(Default value = 21 mA; Minimum value = 20 mA; Maximum value = 22 mA;
Step increments of 0.1 mA)
(1 s to 600 s)
(4 to 20 mA)
(Normal ON; Alerts; All OFF)
(Dim; Low; Medium; High; Bright)
(1 to 1825)
(Enable or Disable)
(Multidrop or Point-to point)
(0 to 63)
(Open/de-energized or 0, closed/energized or 1)
(Open/de-energized or 0, closed/energized or 1)
(Open/de-energized or 0, closed/energized or 1)
(60 to 600 seconds; 0 means no timeout)
(4 digit)
Searchzone Sonik − Technical Manual
9 Mobile App
58
11/2018