Bosch Greensource SM024 Installation, Operation And Maintenance Manual page 13

Greensource cdi series sm model water-to-air heat pumps
Hide thumbs Also See for Greensource SM024:
Table of Contents

Advertisement

Greensource CDi Series SM Model
Fig. 29
7. Rotate the blower into its new position. (See
Fig. 30.)
Fig. 30
8. Remove the remaining vertical blower bracket
by removing the two screws and retain. (See
Fig. 31.)
Fig. 31
9. Remove the blower assembly by sliding it
forward. (See Fig. 32.)
Greensource CDi Series SM Model
The unit's top is notched to allow blower to slide
through.
Fig. 32
10. Remove the blower collar by removing its eight
screws and discard the collar. (See Fig. 33.)
Fig. 33
11. Reorient the blower assembly 180 degree with
the blower "belly" up. (See Fig. 34.)
Fig. 34
12. Slide the blower back into the cabinet. (See
Fig. 35.)
Subject to change without prior notice
Blower Configurations | 13
8733819578 (2019/02)

Hide quick links:

Advertisement

Table of Contents
loading