TA Series Table of Contents TAble of ConTenTS Model Nomenclature ..................3 Initial Inspection ..................4 General Description ..................4 Moving and Storage ..................4 Safety Considerations .................. 4 Location ....................... 4 Installation ....................4 Condensate Drain ..................5 Duct System ....................6 Piping ......................
Initial Inspection TA Series InITIAl InSPeCTIon less than 6 tons, no more than three high. “Do not stack units larger than 6 tons.” Be certain to inspect all cartons or crates on each unit as received at the job site before signing the freight SAfeTY ConSIderATIonS bill.
Mounting Horizontal units TA Series slightly larger than the base to minimize vibration transmission to the building structure. It is not necessary to anchor the unit to the floor. (See Figure #1). MounTInG HorIZonTAl unITS figure #3 pan is usually placed on a plywood base isolated from the ceiling joists by additional layers of vibration absorbing mesh.
Should your well driller express connections. Refer to the Bosch individual data concern regarding the quality of the well water specification sheet for physical dimensions of the available or should any known hazards exist in your collar and flange.
TA Series eCM Interface board Properly sized fuses or HACR circuit breakers must be installed for branch circuit protection. See unit nameplate for maximum fuse or breaker size. The unit is provided with a concentric knock-out in the front left corner post for attaching common trade sizes of conduit, route power supply wiring through this opening.
Page 8
Just above and to the right of the thermostat malfunction relay (Bosch option # 660-006) to connection block are four sets of jumper pins labeled properly energize the light. The relay coil will ADJ, DELAY, HEAT and COOL.
Safety devices and the uPM Controller TA Series any wiring from these connections to avoid anti-short cycle time delay expires. If the low pressure accidental short circuits that can damage unit switch opens 2–4 times in 1 hour, the unit will enter a control components.
- four blinks—Condensate overflow minimum secondary voltage supply. - five blinks—Brownout 3. Bosch recommends the following guidelines for • InTellIGenT reSeT—If a fault condition is initiated, wiring between a thermostat and the unit: 18 GA up the 5 minute delay on break time period is initiated to 60 foot, 16 GA up to 100 ft and 14 GA up to 140 ft.
With the for system flow balancing. Water flow can be accurately Bosch heat pumps these valves are not required. However, set by measuring the water-to-refrigerant heat if installed, a pair of valves are required for proper exchangers water side pressure drop.
System Checkout TA Series SYSTeM CHeCKouT 11. Set the thermostat to maintain the desired space temperature. • After completing the installation, and before 12. Check for vibrations, leaks, etc. energizing the unit, the following system checks should be made: HeAT reCoVerY PACKAGe •...
Water Tank Refill TA Series figure # 9 exceeding sixty (60) feet use 1/2” copper tube. Sepa- 120° F. Depending upon the specific needs of rately insulate all exposed surface of both connecting the customer, you may need to adjust the upper water lines with 3/8”...
Maintenance TA Series TroubleSHooTInG Problem Possible Cause Checks and Corrections No Flow No Power Check power supply Low Flow On/Off Switch Position Set switch to “ON” position Compressor Contactor Engage heat pump contactor Broken or loose wires Repair or tighten wires Air Lock Purge air from piping system Stuck pump shaft/impeller...
Typical Wiring diagram TA Series fIGure 13 TYPICAl WIrInG dIAGrAM Single Phase ECM Blower Motor Revised 03-11 Subject to change without prior notice 6 720 220 046...
Typical Wiring diagram TA Series TYPICAl WIrInG dIAGrAM Single Phase ECM Blower Motor — Electric Heat 6 720 220 046 Subject to change without prior notice Revised 03-11...
Max Fuse Size (Amps) __________________________________ Volts / Amps_____________________ /______________________ Entering Air Temperature _______________________________ Leaving Air Temperature _______________________________ Bosch Group 601 NW 65th Court Fort Lauderdale, FL 33309 Phone: (954) 776-5471 Fax: (800) 776-5529 http://www.fhp-mfg.com Revised 03-11 Subject to change without prior notice...
Troubleshooting TA Series TroubleSHooTInG Problem Possible Cause Checks and Corrections Entire unit Power Supply Off Apply power, close disconnect does not run Blown Fuse Replace fuse or reset circuit breaker. Check for correct fuses Voltage Supply Low If voltage is below minimum voltage specified on unit data plate, contact local power company.
Page 27
Troubleshooting TA Series Insufficient Unit undersized Recalculate heating and or cooling loads. If excessive, possibly adding insulation and shading will rectify the problem cooling or heating Loss of conditioned Check for leaks in duct work or introduction of ambient air through air by leakage doors or windows Airflow...