Table 3. easy-Drive 200L Modbus Map (cont.)
Type
Name
unit16
Latch Close State
unit16
RESERVED
unit16
RESERVED
unit16
RESERVED
unit16
RESERVED
unit16
RESERVED
unit16
RESERVED
unit16
RESERVED
unit16
RESERVED
unit16
RESERVED
unit16
RESERVED
unit16
Test Register - 16 bit
unit32
Test Register - 32 bit
unit16
Span calibration
unit16
RESERVED
unit16
RESERVED
unit16
RESERVED
unit16
RESERVED
unit16
RESERVED
unit16
RESERVED
Loss of signal position
unit16
(100=10.0%)
unit16
Modbus timeout(s)
unit16
Dual contact timeout(s)
24
MB Register
Default
40029
0
40030
40031
40032
40033
40034
40035
40036
40037
40038
40039
40040
45964
40041, 40042
3,012,341,331
40043
0
40044
40045
40046
40047
40048
40049
40050
0
40051
60
40052
60
-continued-
R/W
Values
R
0 - 1
Normally closed latch state
Fixed register to test correct reading of 16 bit registers
R
45964
- Hex=B38C, Binary=1011001110001100
Fixed register to test correct reading of 32 bit registers
R
3,012,341,331
- Hex=B38C AE53, Binary=1011001110001100
1010111001010011
Value of 1 will initiate span calibration. Will
R/W
0,1
automatically set back to 0.
Position to which valve plug will be driven upon loss of
signal. Loss of signal is based upon the active control
mode. 0-1000=0-100.0% with 1 implied decimal point.
R/W
0-1001
In on/off mode 0-499 will result in movement to 0%
while 500-1000 will result in movement to 100%. A
value of 1001 in any control mode is the setting for
"lock-in-last."
Time without a valid Modbus message is seen (to any
address) before "loss of signal" motion is engaged
R/W
0-65535
when in Modbus control mode. Only active in Modbus
control mode.
0=disabled
Time without a digital signal being low (contact made)
from either digital input as viewed by voltage level on
the digital input terminals. If neither contact has been
R/W
0-3600
made (pulled input low) within the timeout period, the
valve plug will be moved to the loss-of-signal position.
Only active in the local, on-off, dual contact mode.
0=disabled.
Instruction Manual
D104331X012
Notes