Table 3. easy-Drive 200L Modbus Map (cont.)
Type
Name
unit16
Modbus address
unit16
Baud Rate
unit16
Parity
unit16
Modbus stop bits
unit16
MSB/LSB
unit16
RESERVED
unit16
Digital I/O selection
unit16
Digital I/O output setup
unit16
Digital I/O input setup
unit16
RESERVED
unit16
RESERVED
unit16
RESERVED
unit16
RESERVED
unit16
RESERVED
unit16
RESERVED
unit16
RESERVED
unit16
RESERVED
unit16
RESERVED
unit16
RESERVED
unit16
RESERVED
unit32
Device Tag
unit32
Valve serial number
unit32
Motor serial number
unit32
Motor revision
unit32
PCB serial number
unit16
PCB revision
unit16
Flash Firmware major revision
unit16
Flash Firmware minor revision
unit16
Flash Firmware mod revision
unit16
Flash Firmware build revision
unit16
Boot Firmware major revision
unit16
Boot Firmware minor revision
unit16
Boot Firmware mod revision
unit16
Boot Firmware build revision
26
MB Register
Default
40074
1
40075
5
40076
0
40077
1
40078
0
40079
40080
1
40081
0
40082
0
40083
40084
40085
40086
40087
40088
40089
40090
40091
40092
40093
Default
40094-40113
tag name
40114, 40115
0
40116, 40117
0
40118, 40119
0
40120, 40121
0
40122, 40123
0
40124
0
40125
0
40126
0
40127
0
40128
0
40129
0
40130
0
40131
0
-continued-
R/W
Values
R/W
1-247
Slave Address of the actuator
4=4800 baud, 5=9600 baud (default), 6=19200 baud,
R/W
4,5,6,7
7=38400 baud
R/W
0,1,2
0=Even, 1=Odd, 2=None
1 stop bit is the standard with even and odd parity
R/W
0,1,2
while 2 stop bits is the standard for none.
R/W
0,1
0=MSB (Big Endian), 1=LSB (Little Endian)
0=9V sinking digital input,
R/W
0,1
1=25 mA at 10V digital output
Valid only when Digital I/O selection is set to Output
R/W
0,1,2,3
(1) - 0=In position, 1=Fully closed, 2=Fully open, 3 =
Remote controlled (driven by Digital Output register)
Valid only when Digital I/O selection is set to Input (0) -
0=Reference only (status appears in 40013 and does
nothing else), 1=Override (status appears in 40013
R/W
0,1
and valve plug is moved to safe position noted in
register 40050)
0 - 255 per
R/W
Device Tag (20 character UTF8 string)
character
0-4,294,967,
Valve assembly serial number assigned at Fisher
R/W*
296
assembly plant
0-4,294,967,
R/W*
Motor/gearbox serial number
296
0-4,294,967,
R/W*
Motor/gearbox revision
296
0-4,294,967,
R/W*
PCB serial number
296
0-4,294,967,
R/W*
PCB revision
296
R
0-65535
From flash firmware when compiled
R
0-65535
From flash firmware when compiled
R
0-65535
From flash firmware when compiled
R
0-65535
From flash firmware when compiled
R
0-65535
From boot firmware when compiled
R
0-65535
From boot firmware when compiled
R
0-65535
From boot firmware when compiled
R
0-65535
From boot firmware when compiled