WebRelay-10 Users Manual
Off Button Label
The text entered in this field appears in the OFF button for the corresponding relay on the Control
Page. Up to 10 characters may be entered in this field. The default text is OFF.
Pulse Button Label
The text entered in this field appears in the 'Pulse' button for the corresponding relay on the Control
Page. Up to 10 characters may be entered in this field. The default text is PULSE.
On Status Text
The text in this field specifies the text that will be displayed in the status field in the Control Page
and in email messages when the corresponding relay is on. Up to 10 characters may be entered in
this field. The default text is ON.
Off Status Text
The text in this field specifies the text that will be displayed in the status field in the Control Page
and in email messages when the corresponding relay switches OFF. Up to 10 characters may be
entered in this field. The default text is OFF.
Pulse Duration
When WebRelay-10 receives a pulse command for the relay, the relay will switch ON for the time
specified in this field. The time is specified in seconds and can range from 0.1 seconds to 86400
seconds in 0.1 second increments. The default time is 1.5 seconds.
Note: When a pulse command is sent through the command interface, the command can include a
pulse time, which will over-ride this value (for that pulse only).
Relay State at Powerup
This drop down menu lets the user specify the state of each of the internal relays when WebRelay-
10 is powered up. The following options can be selected:
- off (unless overridden by event): The relay will be OFF upon power up. This is the default
setting.
- on (unless overridden by event): The relay will be ON when power is applied to
WebRelay-10.
- last state (unless overridden by event) (WebRelay-10 Plus™ only): Upon power up, the
relay will return to its last state when WebRelay-10 Plus™ was powered off.
- input state (unless overridden by event) (WebRelay-10 Plus™ only): The relay will turn
ON upon power up if the input is on.
- opposite input state (unless overridden by event) (WebRelay-10 Plus™ only): The relay
will turn ON upon power up if the input is OFF, or be OFF if the input is ON.
Relay Option (WebRelay-10 Plus™ only)
The inputs can be configured to control the relay. The options in this drop down menu specify how
the input affects the relay.
Note: Input states will only affect the relay at the time the input is changed. Once the change has
taken place the state of the input has no effect on the state of the relay. In other words, if the input
causes the relay to go on, a user may turn the relay OFF from the web browser, even if the input is
still ON.
- no relay control: The input has no effect on the relay.
- set relay equal input 1: When the input is tied to ground, the relay turns ON. When the
input is open, the relay turns OFF.
- set relay opposite of input 1: When the input is tied to ground, the relay turns OFF. When
the input is open, the relay turns ON.
- latch relay when input 1 on (reset via web): When the input is tied to ground, the relay
turns ON. Once the relay is on, it will stay ON (unaffected by input change) until it is turned
OFF manually via the web (or command) by a user or WebRelay-10 Plus™ is powered off.
This option is useful for alarming functions.
- latch relay when input 1 off (reset via web): When the input is open, the relay turns ON.
Once the relay is ON, it will stay ON (unaffected by input change) until it is turned OFF
through a computer command, Control Page, or WebRelay-10 Plus™ is powered off. This
option is useful for alarming functions.
Xytronix Research & Design, Inc.