Write-In Of Word Data (1 Word) - Fuji Electric ZPA Instruction Manual

Infrared gas analyzer, communication functions modbus
Hide thumbs Also See for ZPA:
Table of Contents

Advertisement

6.3
Write-in of word data (1 word) [Function code:06
Function code Max. word number write-in
in one message
06
H
(1)
Message composition
Command message composition (byte)
Station No.
Function code
Write-in designate
No. (relative
address)
Write-in word data
CRC data
(2)
Function explanation
Designated word data is written in write-in designate No. Write-in data are transmitted from master
station in the order of upper and lower bytes.
(3)
Message transmission (example)
The following shows an example of transmitting the "ZERO" key command to No. 1 station.
Key operation command Relative address: 07D0
Command message composition (byte)
Station No.
Function code
Write-in designate
No. (relative
address)
Write-in word data
CRC data
20
Relative data address
0000
1 word
07D0
Upper
Lower
Upper
Lower
Lower
Upper
01
H
06
H
Upper
07
H
Lower
D0
H
Upper
00
H
Lower
40
H
Lower
88
H
Upper
B7
H
Resister No.
-009D
40001-40158
H
H
-07D4
42001-42005
H
H
Response message composition (byte)
Station No.
Function code
Write-in
designate No.
(relative address)
Write-in word
data
CRC data
H
Response message composition (byte)
Station No.
Function code
Write-in designate
No. (relative
address)
ZERO key
Write-in word data
command
CRC data
]
H
Contents
User setting
Operation command
Upper
Lower
Upper
Lower
Lower
Upper
01
H
06
H
Upper
07
H
Lower
D0
H
Upper
00
H
Lower
40
H
Lower
88
H
Upper
B7
H
INZ-TN5A1190-E

Advertisement

Table of Contents
loading

This manual is also suitable for:

ZpbZpg