Normal Operation; Error Codes; Fault Types - Allen-Bradley Micro830 Manual

Hide thumbs Also See for Micro830:
Table of Contents

Advertisement

Error codes

Rockwell Automation Publication 2080-UM002K-EN-E - March 2019
Status Indicator Description
Description
State
9
Network status
Steady Off
Flashing Green
Steady Green
Flashing Red
Steady Red
Flashing Green
and Red

Normal Operation

The POWER and RUN indicators are on. If a force condition is active, the
FORCE indicator turns on and remains on until all forces are removed.
This section lists possible error codes for your controller, as well as recommended
actions for recovery. Information about the fault is stored in a fault log, which can
be accessed from the Diagnostics page in Connected Components Workbench
software. The fault log contains brief information about the last fault, and
detailed information about the last 10 non-recoverable faults that occurred.
If an error persists after performing the recommended action, contact your local
Rockwell Automation technical support representative. For contact information,
go to
http://support.rockwellautomation.com/MySupport.asp

Fault Types

There are two basic types of faults that can occur:
• Recoverable – A recoverable fault can be cleared without having to power
cycle the controller. The fault LED flashes red when a recoverable fault
occurs.
Troubleshooting Appendix E
Indicates
Not powered, no IP address.
The device is powered off, or is powered on but
with no IP address.
No connections.
An IP address is configured, but no Ethernet
application is connected.
Connected.
At least one EtherNet/IP session is established.
Connection timeout (not implemented).
Duplicate IP.
The device has detected that its IP address is being
used by another device in the network. This status
is applicable only if the device's duplicate IP
address detection (ACD) feature is enabled.
Self-test.
The device is performing power-on self-test
(POST). During POST, the network status indicator
alternates flashing green and red. The duration of
the self-test depends on the size of the project in
the controller.