Allen-Bradley Micro830 Manual page 151

Hide thumbs Also See for Micro830:
Table of Contents

Advertisement

Micro830/Micro850/Micro870 24-point Controller HSC Input Wiring Mapping
Modes of Operation
Counter with Internal Direction
(mode 1a)
Counter with Internal
Direction, External Reset and
Hold (mode 1b)
Counter with External
Direction (mode 2a)
Counter with External
Direction, Reset and Hold
(mode 2b)
Two Input Counter (mode 3a)
Two Input Counter with
External Reset and Hold (mode
3b)
Quadrature Counter (mode 4a)
Quadrature Counter with
External Reset and Hold (mode
4b)
Quadrature X4 Counter
(mode 5a)
Quadrature X4 Counter with
External Reset and Hold
Micro830/Micro850 48-point Controller HSC Input Wiring Mapping
Modes of Operation
Counter with Internal Direction
(mode 1a)
Counter with Internal
Direction, External Reset and
Hold (mode 1b)
Counter with External
Direction (mode 2a)
Counter with External
Direction, Reset and Hold
(mode 2b)
Two Input Counter (mode 3a)
Two Input Counter with
External Reset and Hold (mode
3b)
Quadrature Counter (mode 4a)
Rockwell Automation Publication 2080-UM002K-EN-E - March 2019
Input 0 (HSC0)
Input 1 (HSC0)
Input 2 (HSC1)
Input 3 (HSC1)
Input 4 (HSC2)
Input 5 (HSC2)
Input 6 (HSC3)
Input 7 (HSC3)
Count Up
Not Used
Count Up
Not Used
Count Up/Down
Direction
Count Up/Down
Direction
Count Up
Count Down
Count Up
Count Down
A Type input
B Type input
A Type input
B Type input
A Type input
B Type input
A Type input
B Type input
Input 0 (HSC0)
Input 1 (HSC0)
Input 2 (HSC1)
Input 3 (HSC1)
Input 4 (HSC2)
Input 5 (HSC2)
Input 6 (HSC3)
Input 7 (HSC3)
Input 8 (HSC4)
Input 9 (HSC4)
Input 10 (HSC5)
Input 11 (HSC5)
Count Up
Not Used
Count Up
Not Used
Count Up/Down
Direction
Count Up/Down
Direction
Count Up
Count Down
Count Up
Count Down
A Type input
B Type input
Use the High-Speed Counter and Programmable Limit Switch Chapter 8
Input 2 (HSC0)
Input 3 (HSC0)
Input 6 (HSC2)
Input 7 (HSC2)
Reset
Hold
Not Used
Reset
Hold
Not Used
Reset
Hold
Not Used
Z Type Reset
Hold
Not Used
Z Type Reset
Hold
Input 2 (HSC0)
Input 3 (HSC0)
Input 6 (HSC2)
Input 7 (HSC2)
Input 10 (HSC4)
Input 11 (HSC4)
Reset
Hold
Not Used
Reset
Hold
Not Used
Reset
Hold
Not Used
Mode Value in User
Program
0
1
2
3
4
5
6
7
8
9
Mode Value in User
Program
0
1
2
3
4
5
6
137