For example, to enable EII Event 1 and EII Event 3:
EII Event 1 = 4, EII Event 3 = 16
4 + 16 = 20 (enter this value)

UIF - User Interrupt Flush

UIF
UIF
UIF (name or Pin ID)
Enable
or ENO(Pin ID)
IRQType
The UIF instruction is used to flush (remove pending interrupts from the
system) selected user interrupts. The table below shows the types of interrupts
with their corresponding flush bits:
Types of Interrupts Disabled by the UIF Instruction
Interrupt Type
Plug-In Module
Plug-In Module
Plug-In Module
Plug-In Module
Plug-In Module
STI - Selectable Timed Interrupt
STI - Selectable Timed Interrupt
STI - Selectable Timed Interrupt
STI - Selectable Timed Interrupt
EII - Event Input Interrupt
EII - Event Input Interrupt
EII - Event Input Interrupt
EII - Event Input Interrupt
HSC - High-Speed Counter
HSC - High-Speed Counter
HSC - High-Speed Counter
HSC - High-Speed Counter
HSC - High-Speed Counter
HSC - High-Speed Counter
EII - Event Input Interrupt
EII - Event Input Interrupt
EII - Event Input Interrupt
EII - Event Input Interrupt
UFR - User Fault Routine Interrupt
To flush interrupt(s):
1. Select which interrupts you want to flush.
User Interrupts Appendix D
45641
Element
Decimal Value Corresponding Bit
UPM4
8388608
UPM3
4194304
UPM2
2097152
UPM1
1048576
UPM0
524288
STI3
262144
STI2
131072
STI1
65536
STI0
32768
Event 7
16384
Event 6
8192
Event 5
4096
Event 4
2048
HSC5
1024
HSC4
512
HSC3
256
HSC2
128
HSC1
64
HSC0
32
Event 3
16
Event 2
8
Event 1
4
Event 0
2
UFR
1
bit 23
bit 22
bit 21
bit 20
bit 19
bit 18
bit 17
bit 16
bit 15
bit 14
bit 13
bit 12
bit 11
bit 10
bit 9
bit 8
bit 7
bit 6
bit 5
bit 4
bit 3
bit 2
bit 1
bit 0 (reserved)