Rockwell Automation Publication 2080-UM002K-EN-E - March 2019
2. Under Ethernet, click Internet Protocol.
Configure Internet Protocol (IP) settings. Specify whether to obtain the
IP address automatically using DHCP or manually configure IP address,
subnet mask, and gateway address.
The Ethernet port defaults to the following out-of-the box settings:
TIP
• DHCP (dynamic IP address)
• Address Duplicate Detection: On
When a DHCP server fails, the Micro800 controller allocates IP
IMPORTANT
addresses in the private range 169.254.0.1 to 169.254.255.254.
The Micro800 controller verifies its address is unique on the
network using ARP. When the DHCP server is again able to
service requests, the Micro800 controller updates its address
automatically.
3. Click the checkbox Detect duplicate IP address to enable detection of
duplicate address.
4. Under Ethernet, click Port Settings.
5. Set Port State as Enabled or Disabled.
6. To manually set connection speed and duplexity, uncheck the option box
Auto-Negotiate speed and duplexity. Then, set Speed (10 or 100 Mbps)
and Duplexity (Half or Full) values.
7. Click Save Settings to Controller if you would like to save the settings to
your controller.