Rockwell Automation Publication 2080-UM002K-EN-E - March 2019
PTO Output Duty Cycle Error
Turn On/Off time for the Micro830, Micro850, and Micro870 controllers for
the PTO output port is 0.2 µs and 2.5 µs max, respectively. Duty cycle error is:
Positive error = 2.5 µs * F
Negative error = -0.2 µs * F
The plot below shows duty cycle error vs. frequency.
To get the duty cycle error at a certain frequency, for example, the user sets
frequency to 20 kHz, and sets duty cycle to 30% in Connected Components
Workbench software, then actual duty cycle is
+5%
30%
-0.4%.
0.25
0.2
0.15
0.1
0.05
0
-0.05
1000
PTO Typical Readings
PTO Typical Readings
Frequency (kHz)
%Duty Cycle
5
5%
5
10%
5
20%
5
40%
5
55%
100000
10000
Frequency
Expected Duty Cycle
Minimum
Maximum
4.90%
6.25%
9.90%
11.25%
19.90%
21.25%
39.90%
41.25%
54.90%
56.25%
Specifications Appendix A
Positive Error
Negative Error
Typical Duty Cycle
(1.27 KΩ load)
%Duty Cycle
5.48
10.5
20.5
40.5
55.5
235