Hscid (Hscapp.hscid); Hsc Mode (Hscapp.hscmode) - Allen-Bradley Micro830 Manual

Hide thumbs Also See for Micro830:
Table of Contents

Advertisement

Chapter 8
Use the High-Speed Counter and Programmable Limit Switch
140

HSCID (HSCAPP.HSCID)

Description
Data Format
HSCID
Word (UINT)
The following table lists the definition for HSCID.
HSCID Definition
Bits
Description
15...13
HSC Module Type:
0x00: Embedded
0x01: Expansion (not yet implemented)
0x02: Plug-in module
12...8
Module Slot ID:
0x00: Embedded
0x01...0x1F: Expansion (not yet implemented)
0x01...0x05: Plug-in module
7...0
Module internal HSC ID:
0x00-0x0F: Embedded
0x00-0x07: Expansion (not yet implemented)
0x00-0x07: Plug-in module
For Embedded HSC, valid HSCID value is only 0...5.

HSC Mode (HSCAPP.HSCMode)

Description
Data Format
HSC Mode
word (UINT)
The HSCMode variable sets the High-Speed Counter to one of 10 types of
operation. This integer value is configured through the programming device and
is accessible in the control program.
HSC Operating Modes
Mode
Type
Number
0
Up Counter – The accumulator is immediately cleared (0) when it reaches the high
preset. A low preset cannot be defined in this mode.
1
Up Counter with external reset and hold – The accumulator is immediately cleared (0)
when it reaches the high preset. A low preset cannot be defined in this mode.
2
Counter with external direction
3
Counter with external direction, reset, and hold
4
Two input counter (up and down)
5
Two input counter (up and down) with external reset and hold
6
Quadrature counter (phased inputs A and B)
7
Quadrature counter (phased inputs A and B) with external reset and hold
8
Quadrature X4 counter (phased inputs A and B)
9
Quadrature X4 counter (phased inputs A and B) with external reset and hold
User Program Access
read/write
User Program Access
read/write
Rockwell Automation Publication 2080-UM002K-EN-E - March 2019