Use the High-Speed Counter and Programmable Limit Switch
HSC STS (HSC Status) Data
Structure
150
Define a HSC STS data (HSC status information data, data type HSCSTS)
when programming a HSC.

Counting Enabled (HSCSTS.CountEnable)

Description
Data Format
HSCSTS.CountEnable
bit
(1) For Mode descriptions, see
HSC Mode (HSCAPP.HSCMode) on page
The Counting Enabled control bit is used to indicate the status of the
High-Speed Counter, whether counting is enabled (1) or disabled (0, default).

Error Detected (HSCSTS.ErrorDetected)

Description
Data Format
HSCSTS.ErrorDetected
bit
(1) For Mode descriptions, see
HSC Mode (HSCAPP.HSCMode) on page
The Error Detected flag is a status bit that can be used in the control program to
detect if an error is present in the HSC sub-system. The most common type of
error that this bit represents is a configuration error. When this bit is set (1), you
should look at the specific error code in parameter HSCSTS.ErrorCode.
This bit is maintained by the controller and is set when there is an HSC error.
This bit can be cleared by the user, if necessary.
(1)
HSC Modes
User Program Access
0...9
read only
140.
(1)
HSC Modes
User Program Access
0...9
read/write