Acvoor (Ac Voltage Out Of Range); Acvoor In An Entire Branch Or Multiple Branches; When An Entire Branch Or Multiple Branches Are Impacted - enphase M250 Troubleshooting Manual

Hide thumbs Also See for M250:
Table of Contents

Advertisement

ACVOOR (AC Voltage Out of Range)

The microinverter reports that the AC voltage coming from the utility is either too low or too high as
specified by UL standards (UL1741). Acceptable ranges for AC service are shown in the table below:
240 Volt AC Split Phase
L1 to L2
L1, L2 to neutral
An ACVOOR condition should correct itself, as there are often periodic variations in Utility voltage. If the
condition persists, troubleshoot as follows.

ACVOOR in an entire branch or multiple branches

Checks:
1. Measure voltages for L-L and L-N for all phase conductors at the service entrance (PCC), at each
Enphase branch circuit breaker, at each Enphase branch circuit junction box, at each Enphase
branch circuit AC pigtail (if used in this installation), and at the last microinverter of each Enphase
branch circuit.
34
211 to 264 VAC
106 to 132 VAC
 2014 Enphase Energy Inc.
Troubleshooting an Enphase System
208 Volt AC Three Phase
L1 to L2 to L3
L1, L2, L3 to neutral
183 to 229 VAC
106 to 132 VAC
August 2014