INSTALLER'S GUIDE

6. INSTALLATION OF APPLIANCE

INSTALLATION
6.1 Fireplace size
The fireplace must comply with the requirements described in section 4.
6.2
Fireplace flue pull.
Visually inspect the flue for any obstruction, and that a smooth transition from the
fireplace opening into the flue is available. Close all doors and windows in the
room in which the appliance is to be installed. After confirming with a match that
smoke is drawn into the flue, light a 13 gram smoke pellet and check that there is a
definite flow through the flue. Verify outside that the smoke exits from one
terminal only and that the termination is suitable. Observe, where possible, upstairs
rooms and loft spaces for signs of escaping smoke indicating a defective flue. If
there is not a definite flow warm the flue for a few minutes and repeat the smoke
pellet test. If there is still no definite flow the flue may need remedial work – Do
not fit the appliance until there is a definite flow through the flue.
IMPORTANT
Before continuing with the installation of this gas fire the aeration setting
on the burner must be checked. This is factory set. See section 11
(Servicing and parts replacement).