Parameter list
VLT 6000
PNU
Parameter
#
description
400
Reset function
401
Automatic restart time
402
Flying start
403
Sleep mode timer
404
Sleep frequency
405
Wake up frequency
406
Boost setpoint
407
Switching frequency
408
Interference reduction method
409
Function in case of no load
410
Function at mains failure
411
Function at overtemperature
412
Trip delay overcurrent, I
413
Minimum feedback, FB
414
Maximum feedback, FB
415
Units relating to closed loop
416
Feedback conversion
417
Feedback calculation
418
Setpoint 1
419
Setpoint 2
420
PID normal/inverse control
421
PID anti windup
422
PID start-up frequency
423
PID proportional gain
424
PID integration time
425
PID differentiation time
426
PID differentiator gain
limit
427
PID lowpass filter time
48
VLT
®
5000/5000 Flux/6000 HVAC/8000 AQUA PROFIBUS
Factory setting
Manual reset
10 sec.
Disable
Off
0 Hz
50 Hz
100%
Depends on the unit
ASFM
Warning
Trip
Trip
60 sec
LIM
0.000
MIN
100.000
MAX
%
Linear
Maximum
0.000
0.000
Normal
On
0 Hz
0.01
Off
Off
5.0
0.01
Range
Changes 4-Setup
during operation
Yes
0 - 600 sec.
Yes
Yes
0 - 300 sec.
Yes
f
- Par. 405
Yes
MIN
Par. 404 - f
Yes
MAX
1 - 200 %
Yes
3.0 - 14.0 kHz
Yes
Yes
Yes
Yes
Yes
0 - 60 sec.
Yes
-999,999.999 - FB
Yes
MIN
FB
- 999,999.999 Yes
MIN
Yes
Yes
Yes
FB
- FB
Yes
MIN
MAX
FB
- FB
Yes
MIN
MAX
Yes
Yes
f
- f
MIN
MAX
0.00 - 10.00
Yes
0.01 - 9999.00 s. (Off) Yes
0.0 (Off) - 10.00 sec. Yes
5.0 - 50.0
Yes
0.01 - 10.00
Yes
MG.90.D1.02
– VLT is a registered Danfoss trademark
Conversion
index
0
Yes
0
Yes
-1
Yes
0
Yes
-1
Yes
-1
Yes
0
Yes
2
Yes
0
Yes
0
Yes
0
Yes
0
Yes
0
Yes
-3
Yes
-3
Yes
-1
Yes
0
Yes
0
Yes
-3
Yes
-3
Yes
0
Yes
0
Yes
-1
-2
Yes
-2
Yes
-2
Yes
-1
Yes
-2
Yes